background image

7. The electrical control settings should be checked and, if

To prevent moisture entering the system and

necessary, reset to those settings indicated on the wiring

contaminating the oil extra care is necessary.  Follow

diagram.  Safety controls are factory set and must be

the enclosed procedure to add or remove oil from the

maintained at settings indicated on the wiring diagram.

system.

8. The temperatures of the chilled water both in and out,

The holding tank must be clean and free of any

should be checked to insure the unit is operating within

moisture.  (Evacuate tank to 200 microns).  The holding

the desired temperatures.

tank can be a receiver or reclaiming tank of a size large

MAINTENANCE

withstand the operating pressure of the system.  When

CONDENSER

supplied to a holding tank and then evacuated through

Units are equipped with direct drive fans that have inherently

the vapor port down to 200 microns.  Do not allow the

protected motors with permanently lubricated bearings.

container to vent to the atmosphere as the transfer must

The air inlet of the condenser coil should be kept clean

required.

through a regular maintenance program.

COMPRESSOR

1. OIL LEVEL - The oil level in the compressor(s) should be

checked periodically, with the compressor stopped.
Stage the unit down until all compressors are off and
check the compressor crankcase sight glass for oil level.
If the oil level is below one half (1/2) the sight glass, oil
must be added.

2. A.

RECOMMENDED OIL FOR R-22 MACHINES
Compressor Model Series SSCA - The compressor
is factory charged with DB Karlube #10 Oil. 
Compressor Model Series SSCB - The compressor
is factory charged with DB Karlube #21 Oil.

Do not mix above oils or attempt to operate the
screw compressor with any other oil. It is
suggested that a gallon or more of the appropriate
oil be obtained and kept at the job site.
DB Karlube #10
DB Karlube #21

B.

RECOMMENDED OIL FOR R407C MACHINES
DO NOT USE DB Karlube #10.
Compressor Models SSCA use DB Karlube #16
Oil.
Compressor Models SSCB use DB Karlube #21
Oil.  
Contact factory for price.

The above-listed oils are synthetic lubricants of the
Polyol Ester (POE) type.  Due to the complex
nature of the POE, great precaution must be taken
to prevent any moisture from entering the system
when servicing or adding oil.  POE oil has a
greater solvency for water.  Water reacts
chemically with the ester to form acids and
alcohols in a process called "hydrolysis".  POE
molecules attract moisture.  Moisture removal by
evacuation is more difficult because the POE
"holds water more tightly" than mineral oil.
Moisture causes corrosion and copper plating at an
unacceptable, high level.  This reaction occurs
where temperatures are the highest within the
compressor.

enough for the total oil change and must be able to

adding oil, it should be transferred from the container

be done through a closed loop.  An oil pump will be

PROCEDURE FOR ADDING OIL
Manually close liquid line service valve.  Lower return
water T-stat (4TAS) setting to start the compressor.  Run
compressor until unit shuts down on low pressure.  Place
the control circuit on/off switch in the off position.  Locate
the high pressure port adjacent to solenoid valve UL-3
(see drawing page 8) and remove the cap.  Attach oil
pump to holding tank high pressure port.  Pump oil into
this port until the oil level is 1/2 of the sight glass.

Replace the port cap, open the liquid line shut off valve
and place the control circuit on/off switch in the on
position.  Set the operating T-stat to the normal operating
temperature and reset the low pressure switch.

Oil can also be added, through the suction port of the
compressor, while running the compressor.

3. COMPRESSOR REPAIRS (Internal) - Contact factory or

an authorized DB Service Agency if a compressor
malfunction is suspected.

4. COMPRESSOR REPAIRS (External) - Proper operation

of unloaded start, loading, and unloading is controlled by
solenoid valves UL-1, UL-2 and UL-3.  Any of these three
(3) solenoid valves may be repaired or replaced in the
field, as required.  Also the compressor crankcase heater
may be replaced.

5. Standard oil acid test kit is not compatible with synthetic

oil.  See DB color chart for oil condition.

7

Summary of Contents for ACDX

Page 1: ...ctions 6 ACDX Operation Start up 6 7 Maintenance 7 Slide Valve Unloading Operation 8 Low Ambient Operation 9 Fan Position Numbers 10 Fan Cycling Sequence 11 ACDX Sequence of Operation 12 Electrical Co...

Page 2: ...rs attention to the instructions contained herein it will give To use this manual effectively you must first identify your unit model from the unit nameplate It is assumed the user of this manual and...

Page 3: ...eration Weight 3592 4732 5044 7712 9684 10726 MODEL SIZE 150 170 185 210 235 255 Compressor Model Qty SSCA060 3 SSCA075 3 SSCA060 4 SSCA075 4 SSCA060 1 SSCA060 2 SSCA075 2 SSCA075 2 Displ CFH Compr 72...

Page 4: ...cables or other moving equipment are placed so as to avoid damage to the unit or piping The refrigerant Under certain critical conditions it may be necessary to piping must not be used as a ladder or...

Page 5: ...microcomputer controlled units conjunction with a spring loaded bypass regulating valve as shown in Figure 1B The bypass valve must be set to Water Quality ACDX Coolers used in these packages are ass...

Page 6: ...5 TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLED WATER CONNECTIONS PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 7: ...ump temperature must be at a The unit is ready for start up when the following procedures representative This will ensure that the oil is warm have been completed enough to vaporize any dissolved refr...

Page 8: ...Compressor Models SSCB use DB Karlube 21 Oil Contact factory for price The above listed oils are synthetic lubricants of the Polyol Ester POE type Due to the complex nature of the POE great precaution...

Page 9: ...en or close UL 1 and UL 2 in response to the supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to the oil return...

Page 10: ...ell as that portion of the surface rejecting heat by natural convection with related fans off To further assist low ambient starts all fans are held off until the head pressure reaches 190 psig This a...

Page 11: ...C1 1 3 5 7 9 11 C2 2 4 6 8 10 12 150 1 2 150 3 C1 1 3 5 7 9 11 13 15 C3 C2 2 4 6 8 10 12 14 16 Front Rear 170 1 2 170 3 185 1 2 185 3 C1 1 3 5 7 9 11 13 15 17 C3 C2 2 4 6 8 10 12 14 16 18 Front Rear...

Page 12: ...1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 185 1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 210 1 LH 1 3 5 7 9 Rear Module 1 RH 2 4 6 8 1...

Page 13: ...M1 1 opens to de energize oil light is not on disconnect the main power and reverse sump heater 1HTR and switch 1M1 2 closes to any two phase legs at the Main Incoming Power activate the fan control c...

Page 14: ...ed Compressor No 2 will not be able to restart for five minutes due to integral time delays SAFETY CONTROLS The unit is protected by the following safety controls 8 Water Flow Switch FLS 1 High Pressu...

Page 15: ...occurs temperature during the compressor off when ambient temperature is below 40EF cycle preventing refrigerant migration in 3TAS is measuring ambient temperature to the crankcase and consequent and...

Page 16: ...ges 27 1TAS Motor Overload Protection Compressor overload protection is 1 Unit Control Contact Unit on off control should be provided by a solid state device 1TAS done through the terminals shown on t...

Page 17: ...ps Electrically Programmable Read Only an NC25 microcomputer system The computer Memory store general operating procedures system is composed of a main microcomputer algorithms and is the same for all...

Page 18: ...nce midnight and the accumulated run time during yesterdays Y twenty four hour period CYC gives the number of times that the control point cycled off since midnight If a feedback digital input is asso...

Page 19: ...then new calibration would be 58 60 3 1 3 3 3 So the zero calibration should be changed to 3 1 You must be authorized See Section 3 4 2 Select DATE TIME SET on the main menu Press ENTER to display cur...

Page 20: ...r start delay 7 Power loss reset 8 Anti recycle timing 9 Low pressure safety 19 11 Freeze safety 12 High Oil Temp Safety 13 Alarm Output 14 Fan control 15 Chilled water reset and customer control inte...

Page 21: ...rough 4 for each compressor number manual control DO NOT start a compressor 7 Add the value obtained in step 5 to the amps calculation A setpoint value from step 6 NOTE All compressors will revert bac...

Page 22: ...rator pressure of a given Sample Ramp Times Minutes For a Two pressure B setpoint a time delay is initiated If Compressor Unit with a 2 Second Compressor the pressure stays below the setpoint during t...

Page 23: ...ow normal compressor control if the unit schedule is calling for unit operation that a compressor auxiliary contact digital input stays ON for 15 seconds when the computer is commanding the compressor...

Page 24: ...e pressed after the problem is resolved HOLD state If the discharge pressure 4 23 Low Chiller Flow Alarm A low flow alarm will be generated if a compressor control point is ON and the flow switch digi...

Page 25: ...TYPICAL POWER WIRING ACDX120A...

Page 26: ...TYPICAL CONTROL WIRING ACDX120A...

Page 27: ...TYPICAL OPTIONS WIRING ACDX120A...

Page 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Page 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Page 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...

Page 31: ...5 472 12 1 5 5 9 400 3 4 1120 9 3 460 257 350 75 2 98 539 180 12 1 5 3 0 400 3 4 1120 9 3 150 230 570 700 60 3 152 1228 409 16 1 5 5 9 600 5 0 1120 9 3 208 632 800 60 3 171 1228 409 16 1 5 5 9 600 5 0...

Page 32: ...Cooler Model Curve No Min GPM Max GPM 040 CHSO10601B 1 78 315 050 CHS011601B 1 86 315 060 CHS013601B 2 101 420 080 EXD14102J09 3 140 440 095 EXD16112J09 4 175 519 120 EXD16122J07 5 236 697 150 EXT181...

Page 33: ......

Page 34: ...ACDX AUDX CONDENSER CLEARANCE...

Page 35: ......

Page 36: ...ACDX LOAD POINTS...

Page 37: ...ACDX RUBBER IN SHEAR ISOLATOR...

Page 38: ...ACDX SPRING ISOLATOR...

Page 39: ...AUDX LOAD POINTS...

Page 40: ...AUDX RUBBER IN SHEAR ISOLATOR...

Page 41: ...AUDX SPRING ISOLATOR...

Page 42: ...4 Clean the condenser 5 Compressor discharge check valve not operating 5 Replace if necessary properly 6 Fans not running 6 Check pressure control setting condenser pressure exceeds saturated pressure...

Page 43: ...Start Up a Open compressor discharge service valve if supplied b Open liquid valve s c Open suction and discharge valves to pressure gauges if supplied d Check rotation of all fan motors e Start auxi...

Page 44: ...101 Burgess Road Harrisonburg VA 22801 PH 540 434 0711 FAX 540 434 4595 Printed in U S A I O 6193A Issued 9 98...