Calibrating flow rates
The DucoBox Energy Comfort calibration mode can be activated using the display menu�
IMPORTANT, BEFORE CALIBRATING
Close all windows and doors. Ensure that all duct openings in the DucoBox Energy Comfort are fully closed and
that the DucoBox Energy Comfort cover is closed! Avoid air leaks in the ventilation ducts. Open all interior doors
between the various zones.
Calibrating the DucoBox Energy Comfort
1
Activate advanced mode:
• Scroll down to
ADVANCED
and press enter�
• Enter the installer’s code
9876
and press enter�
2
Scroll down to
CALIBRATION
→
WIZARD
and press enter� The DucoBox Energy
Comfort calibration mode starts up� Do not start manual calibration until you see
the message on the display and follow the instructions on screen� Enter the flow
rates for each zone if asked to do so�
3
In the ‘Adjust the supply vents’ step, select the duct with the highest flow rate
and resistance and, using a pressure-compensated air flow meter, measure the
flow rate at this vent� If the flow rate is too high or too low, you can adjust it using
the arrow keys on the DucoBox Energy Comfort� Depending on the user controller
version, this can also be done by pressing the (lower) and (higher) buttons on
a paired user controller� Adjust the flow rate so as to obtain the desired flow rate at
this vent� The flow rate can be fine-adjusted at the vent�
NOTE
: The system needs around ten seconds to run stably when adjusting the
flow rate using the buttons on the DucoBox Energy Comfort, User controller or
making large changes at the vent. The system will indicate when the calibration
is stable. The flow rate cannot be measured correctly until after this time has
elapsed.
/
/
4
Proceed now with the remaining supply vents� The flow rate from these other
vents must only be adjusted at the vents themselves. Adjusting vents will not
alter the flow from previously calibrated vents�
5
You will need to press the enter button ( ) on the DucoBox Energy Comfort once
all supply vents have been calibrated� Otherwise you can confirm by long-pressing
the AUTO button on the User controller�
Calibrating
exhaust
vents
6
Repeat steps
3
to
5
inclusive for all exhaust vents�
09.C
Verification
The calibrated flow rates can be checked at the various vents once adjustment and calibration have been completed� Do this by
going into advanced mode (see page 25) and select “
CALIBRATION
→
VERIFY HIGH LEVEL
”� The DucoBox Energy Comfort venti-
late for 30 min at its calibrated ventilation setting�