Calibrating flow rates

The DucoBox Energy Comfort calibration mode can be activated using the display menu�

IMPORTANT, BEFORE CALIBRATING

Close all windows and doors. Ensure that all duct openings in the DucoBox Energy Comfort are fully closed and 

that the DucoBox Energy Comfort cover is closed! Avoid air leaks in the ventilation ducts. Open all interior doors 

between the various zones.

Calibrating the DucoBox Energy Comfort

1

Activate advanced mode:

• Scroll down to 

ADVANCED

 and press enter

• Enter the installer’s code 

9876

 and press enter

2

Scroll down to 

CALIBRATION

 → 

WIZARD

 and press enter� The DucoBox Energy 

Comfort calibration mode starts up� Do not start manual calibration until you see 

the message on the display and follow the instructions on screen� Enter the flow 

rates for each zone if asked to do so�

3

In the ‘Adjust the supply vents’ step, select the duct with the highest flow rate 

and resistance and, using a pressure-compensated air flow meter, measure the 

flow rate at this vent� If the flow rate is too high or too low, you can adjust it using 

the arrow keys on the DucoBox Energy Comfort� Depending on the user controller 

version, this can also be done by pressing the   (lower) and   (higher) buttons on 

a paired user controller� Adjust the flow rate so as to obtain the desired flow rate at 

this vent� The flow rate can be fine-adjusted at the vent�

NOTE

: The system needs around ten seconds to run stably when adjusting the 

flow rate using the buttons on the DucoBox Energy Comfort, User controller or 

making large changes at the vent. The system will indicate when the calibration 

is stable. The flow rate cannot be measured correctly until after this time has 

elapsed.

 / 

 / 

4

Proceed now with the remaining supply vents� The flow rate from these other 

vents must only be adjusted at the vents themselves. Adjusting vents will not 

alter the flow from previously calibrated vents�

5

You will need to press the enter button ( ) on the DucoBox Energy Comfort once 

all supply vents have been calibrated� Otherwise you can confirm by long-pressing 

the AUTO button on the User controller�

Calibrating 

exhaust

 vents

6

Repeat steps 

3

 to 

5

inclusive for all exhaust vents�

09.C

Verification

The calibrated flow rates can be checked at the various vents once adjustment and calibration have been completed� Do this by 

going into advanced mode (see page 25) and select “

CALIBRATION

 → 

VERIFY HIGH LEVEL

”� The DucoBox Energy Comfort venti-

late for 30 min at its calibrated ventilation setting�

Summary of Contents for DucoBox Energy Comfort 325

Page 1: ...Installation guide ENGLISH DucoBox Energy Comfort L2000782 Revision B 1 25 03 2020...

Page 2: ...17 08 A Pairing components 17 08 B Removing replacing components 18 08 C Tips 18 09 Air side calibration 19 09 A Pre setting vents 19 09 B Calibrating flow rates 20 09 C Verification 20 09 D Copy cali...

Page 3: ...t 325 0000 4485 Optional accessories Product Item number Siphon flat Energy Eco 0000 4376 Communication Print 0000 4251 Humidity Box Sensor Energy Comfort 0000 4545 Mounting chair upright Energy Comfo...

Page 4: ...heat exchanger This prevents the heat exchanger from freezing up If the imbalance is insufficient to prevent it from freezing up then the unit will be temporarily switched off Constant Flow The unit...

Page 5: ...w at maximum flow rate 100 Pa 111 5W 111 5W 111 5W 111 5W Power at 50 Pa reference flow rate 47 9 W 47 9 W 47 9 W 47 9 W Sound power level Lwa 55 dB A 55 dB A 55 dB A 55 dB A Reference flow rate Qref...

Page 6: ...stall connect and commission the DucoBox Energy Com fort as set out in this manual Keep the manual close to your unit Maintenance instructions must be followed closely in order to avoid damage and or...

Page 7: ...connections 5 Wall mounting hanger bracket 6 Control unit with integrated user controls 7 Cap of the air filter 8 Cap of the air filter 9 Bypass valve 10 Power cable 230 VAC 11 Pressure sensor 12 Pre...

Page 8: ...the op tion of allowing the Duco ventilation systems to commu nicate via ModBus and or ethernet ModBus integration enables them to be linked to a building management system Linking the Duco Ventilati...

Page 9: ...Sensor or one of the connections on the optional Communi cation Print see page 8 05 A Cabling diagram Loosen the screws 1 Slide the cap forwards 2 Cut one or more or the specified pieces away from th...

Page 10: ...m free field less through obstacles Maximum number of components Up to 25 wireless components in a single system 05 D Wired cabled communication Wired components can be daisy chained recommended This...

Page 11: ...er months Take care to ensure that the air inlet is accessible for any cleaning that may be required A smaller cross sectional area bore can actually have a major detrimental impact on system performa...

Page 12: ...ll ensure it is hanging level when doing so Ensure at the same time that the screws and plugs are suitable for the substrate and the weight of the unit 21 kg screws and plugs not included in the suppl...

Page 13: ...ge duct of the DucoBox Energy Comfort and centrally measures the humidity of the air discharged from the house A DucoBox Energy Comfort contains a maximum of one box sensor Connecting the Humidity Box...

Page 14: ...to ensure that the supply and exhaust vents are a minimum of 1 5 m van apart so they cannot come into contact It is preferable not to fit a vent right next to a wall in order to prevent soiling In ord...

Page 15: ...the first time you will be asked to enter a few basic settings Navigate using the arrow keys and and confirm using enter General settings LEFT HAND RIGHT HAND setting The LEFT HAND RIGHT HAND setting...

Page 16: ...hese steps you can proceed with the following steps in order to complete the installation Pairing control components with the DucoBox Energy Comfort Electrical system see page 17 DucoBox Energy Comfor...

Page 17: ...run again if additional control components need to be paired at a later stage All previously paired components will be retained in the network LED indications Colour Blinking installation mode On con...

Page 18: ...l buttons on a paired control The LED will flash green rapidly 5 sec 2 Press briefly twice on the button of the component to be replaced 2x OLD 3 Tap once on the button for the new component The latte...

Page 19: ...mended for supply vents in order to prevent excessive noise from being genera ted For this reason it is recommended that the flow be split between different vents for higher flow rates SITUATION 1 One...

Page 20: ...x Energy Comfort Depending on the user controller version this can also be done by pressing the lower and higher buttons on a paired user controller Adjust the flow rate so as to obtain the desired fl...

Page 21: ...Make sure that all valves are adjusted identically presetting fine tuning for each installation 2 Activate advanced mode Scroll down to ADVANCED and press enter Enter the installer s code 9876 and pr...

Page 22: ...be visible after that Operation The display on the DucoBox Energy Comfort is equipped with three 3 buttons up down and enter The arrow keys can be used to scroll through the menu If the display has n...

Page 23: ...ng the arrow keys will enable changing the ventilation position Open the menu via enter The selected ventilation position on the unit is permanent indicated in purple in Controls until the user activa...

Page 24: ...across the heat exchanger or not at all Fresh outdoor air will therefore not be heated up by warm stale indoor air This relatively cooler outdoor air entering the house will be used to reduce the tem...

Page 25: ...dicates that advanced mode is active The menu will exit advanced mode after 30 minutes of inactivity or after restarting the DucoBox Energy Comfort Advanced mode can also be closed down manually using...

Page 26: ...E VERSION for information In any communication with Duco you may be asked to state the software version of your DucoBox Energy Comfort Please keep this number to hand for any communication SERVICE COD...

Page 27: ...products seller Keep the serial number of your product to hand The serial number is on the sticker at the top of the DucoBox Energy Comfort 12 Warranty All warranty conditions concerning the DucoBox...

Page 28: ...Installed by L2000782 Document last modified on 25 03 2020 revision B 1...

Reviews: