L2000782 Installation guide for DucoBox Energy Comfort (Revision B.1 | 25.03.2020)
09
Air-side calibration
Calibrating the DucoBox Energy Comfort can be split into various steps:
1� Pre-setting supply and exhaust vents
2� Calibrating flow rates
The system needs to be configured for it to work correctly.
This will ensure its operation is as quiet as possible and energy-efficient.
09.A
Pre-setting vents
The exhaust and supply vents are installed in a moisture-laden/stale air extraction or fresh air supply duct� In order to calibrate the
air supply and exhaust correctly, these vents must be set depending on the situation in accordance with the table below�
A maximum of 50 m³/h is recommended for
supply
vents in order to prevent excessive noise from being genera-
ted. For this reason it is recommended that the flow be split between different vents for higher flow rates.
SITUATION 1
:
One vent per zone
SITUATION 2
:
Multiple vents per zone
with
equal flow rates
SITUATION 3
:
Multiple vents per zone with
different flow rates
Set all vents to the fully
open position, regardless of
the desired flow rate�
Set all vents to the fully
open position, regardless of
the desired flow rate� With
DucoVent Design vents, turn
the cone on the trim plate to
the fully open position�
Set the vents so they match the desired flow rate in accordance
with the table�
EXAMPLE:
Zone
1
Zone
2
EXAMPLE:
Zone 1
EXAMPLE:
Zone 1
+
DUCOVENT
DESIGN
DUCOVENT BASIC
AND OTHER VENTS
100%
open
50%
open
25%
open
When using DucoVent Design exhaust vents, always leave at least the outer ring in
place for acoustic effect.
Foam