Specification
Page 17 of 100
057-230 ISSUE: 1
2.8.4
MAGNETIC PICKUP
NOTE: DSE can supply a suitable magnetic pickup device, available in two body thread
lengths:
DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2
½” thread length
DSE Part number 020-013 -
Magnetic Pickup probe 5/8 UNF 4” thread length
Type
Differential input
Minimum Voltage
0.5 V RMS
Max Common Mode Voltage
±2 V
Maximum Voltage
Clamped to ±70 V by transient suppressers, dissipation not to
exceed1 W.
Maximum Frequency
10,000 Hz
Resolution
6.25 RPM
Accuracy
±25 RPM
Flywheel Teeth
10 to 500
Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one device
can often supply the signal to both the DSE module and the engine governor. The possibility of this
depends upon the amount of current that the magnetic pickup can supply.
2.9 OUTPUTS
2.9.1
DC OUTPUTS A & B (FUEL & START)
Type
Normally used as Fuel & Start outputs.
Fully configurable for other purposes if the module is configured to control an
electronic engine.
Rating
10 A resistive for 10 secs, 5 A resistive continuous at 35 V
2.9.2
CONFIGURABLE DC OUTPUTS C, D, E & F
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
2 A resistive continuous at 35 V