Installation
Page 31 of 100
057-230 ISSUE: 1
3.1.3
GENERATOR / MAINS VOLTAGE & FREQUENCY SENSING
NOTE: Terminals 29 to 32 not fitted to DSE6010 MKII
NOTE: The above table describes connections to a three phase, four wire alternator. For
alternative wiring topologies, please see the Alternate Topology Wiring Diagrams section of
this manual.
Pin
No
Description
Cable
Size
Notes
25
Generator L1 (U) Voltage
Monitoring
1.0 mm²
AWG 18
Connect to generator L1 (U) output (AC)
(Recommend 2A fuse)
26
Generator L2 (V) Voltage
Monitoring
1.0 mm²
AWG 18
Connect to generator L2 (V) output (AC)
(Recommend 2A fuse)
27
Generator L3 (W) Voltage
Monitoring
1.0 mm²
AWG 18
Connect to generator L3 (W) output (AC)
(Recommend 2A fuse)
28
Generator Neutral (N) Input
1.0 mm²
AWG 18
Connect to generator Neutral terminal (AC)
29
Mains L1 (R) Voltage Monitoring
1.0 mm²
AWG 18
Connect to Mains L1 (R) output (AC)
(Recommend 2A fuse)
30
Mains L2 (S) Voltage Monitoring
1.0 mm²
AWG 18
Connect to Mains L2 (S) output (AC)
(Recommend 2A fuse)
31
Mains L3 (T) Voltage Monitoring
1.0 mm²
AWG 18
Connect to Mains L3 (T) output (AC)
(Recommend 2A fuse)
32
Mains Neutral (N) Input
1.0 mm²
AWG 18
Connect to Mains Neutral terminal (AC)
3.1.4
CURRENT TRANSFORMERS
WARNING!: Do not disconnect this plug when the CTs are carrying current. Disconnection
open circuits
the secondary of the C.T.’s and dangerous voltages may then develop. Always
ensure the CTs are not carrying current and the CTs are short circuit connected before making
or breaking connections to the module.
NOTE: The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden
of the controller, the cable length being used and any other equipment sharing the CT. If in
doubt, consult your CT supplier.
Pin
No
Description
Cable
Size
Notes
33
CT Secondary for L1
2.5 mm²
AWG 13
Connect to s1 secondary of L1 monitoring CT
34
CT Secondary for L2
2.5 mm²
AWG 13
Connect to s1 secondary of L2 monitoring CT
35
CT Secondary for L3
2.5 mm²
AWG 13
Connect to s1 secondary of L3 monitoring CT
36
CT Common
2.5 mm²
AWG 13
Connect to s2 secondary of L1, L2 & L3 monitoring CTs and
ground
37