Description Of Controls
057-230 ISSUE: 1
Page 44 of 100
Icon
Description
Auto
Mode
This button places the module into its
Auto Mode
. This mode allows the module
to control the function of the generator automatically. The module monitors the
remote start
input and once a start request is made, the set is automatically started
and placed on load
(Close Generator and Delayed Load Output 1, 2, 3 & 4 become
active in order from lowest to highest (if used))
.
Upon removal of the starting signal, the module removes the load from the
generator and shut the set down observing the
stop delay
timer and
cooling
timer
as necessary
(Close Generator and Delayed Load Output 1, 2, 3 & 4 become
inactive at once (if used))
. The module then waits for the next start event.
For further details, please see section entitled Operation elsewhere in this manual.
Alarm Mute / Lamp Test
This button de-activates the audible alarm output (if configured) and illuminates all
of the LEDs on the module’s facia.
Start
This button is only active in the
Stop/Reset Mode
,
Manual
Mode
and
Test Mode
.
Pressing the
Start
button in
Stop/Reset Mode
powers up the ECU but does
not start the engine. This can be used to check the status of the CAN
communication and to prime the fuel system.
Pressing the
Start
button in
Manual
Mode
or
Test Mode
starts the
generator and runs it off load in
Manual
Mode
or on load in
Test Mode
.