DSE Model 7560 ATS and Mains Controller Operators Manual
52 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
9 FAULT FINDING
SYMPTOM
POSSIBLE REMEDY
Unit is inoperative
Check the battery and wiring to the unit. Check the DC
supply. Check the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9
Volts when the module is operating. Run the system
through a complete test and check the voltage remains
within these limits consistently.
Check the operating temperature is not above 70°C. Check
the DC fuse.
Warning fault operates
Check relevant switch and wiring of fault indicated on LCD
display. Check configuration of input.
Continuous starting of generators
when in AUTO
Check that there is no signal present on the “Remote Start”
input. Check configured polarity is correct. Check that the
mains supply is within limits and load level on the mains is
not above the configured level for mains “import/export”.
NOTE: - The above fault finding is provided as a guide check-list only. As it is possible
for the module to be configured to provide a wide range of different features always, refer to
the source of your module configuration if in doubt.