DSE Model 7560 ATS and Mains Controller Operators Manual
057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM 35
6.2.3 RUNNING IN PARALLEL
RUNNING IN LOAD DEMAND
If the module is configured for running in load demand, sets will be started and stopped
automatically on changing load levels.
NOTE: - If the load is reduced to zero (0kW) then the genset(s) with the highest priority
will remain running.
REMOTE START IN ISLAND MODE
If the module is configured for remote start in island
mode, the load is then ramped fully onto the generators.
The 7560 will display:
Status
Ramp onto bus
76% kW 80% kVAr
Auto mode
Once the mains loading has reached 0kW, the bus load
switch will be opened and the 7560 will display:
Status
Bus on load
Auto mode
Should the remote start signal be deactivated, the
module will first initiate a return timer to ensure that it is
not a transient condition. The 7560 will display:
Status
Return delay
00:05
Auto mode
NOTE: - Should a call to start become active again, the module will continue to run the
generators on load and ignore the fluctuating “call to stop” until such a time as it remains inactive for
the duration of the return delay timer.