4.2.5 MAINS AND BUS CURRENT TRANSFORMERS
WARNING!:- Do not disconnect this plug when the CTs are carrying current.
Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may
then develop. Always ensure the CTs are not carrying current and the CTs are short circuit
connected before making or breaking connections to the module.
NOTE:- The DSE7510 MK1 module has a burden of 0.5VA on the CT. Ensure the CT is
rated for the burden of the DSE7510 MK1 controller, the cable length being used and any
other equipment sharing the CT. If in doubt, consult your CT supplier.
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
51
CT Secondary for Mains L1
2.5mm²
AWG 13
Connect to s1 secondary of L1 monitoring CT
52
CT Secondary for Mains L2
2.5mm²
AWG 13
Connect to s1 secondary of L2 monitoring CT
53
CT Secondary for Mains L3
2.5mm²
AWG 13
Connect to s1 secondary of L3 monitoring CT
Connection to terminals 54 & 55
The function of terminals 54 and 55 change position depending upon wiring topology as follows :
Type
Topology
Pin
No
Description
CABLE
SIZE
7300
series
No earth fault measuring
54
DO NOT CONNECT
55
Common for CTs connected to
L1,L2,L3
2.5mm²
AWG 13
Restricted earth fault measuring
54
Common for CTs connected to
L1,L2,L3,N
2.5mm²
AWG 13
55
Connect to CT on the neutral
conductor
2.5mm²
AWG 13
Un-restricted earth fault measuring
(Earth fault CT is fitted in the neutral to
earth link)
54
DO NOT CONNECT
55
Common for CTs connected to
L1,L2,L3
2.5mm²
AWG 13
NOTE:- Take care to ensure correct polarity of the CT primary as shown below. If in
doubt, check with the CT supplier.
CT labelled as
p1,
k
or K
CT labelled as
p2,
l
or L
To Supply
To Load