DSE Model 7560 ATS and Mains Controller Operators Manual
30 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
CLOSE MAINS
This push button is used to control the closure of the mains load switching
device and has two modes of operation :
1. Synchronising is NOT enabled. Pressing this button when the mains is
available off load and in MANUAL mode, the bus load switch is opened
and the mains load switch is closed. Further presses of this button will
have no effect.
2. Synchronising is enabled. Pressing this button when the mains is
available and in MANUAL mode, the 7510MK1 controller, will volts
match and synchronise with the Bus. The mains load switch is then
closed in parallel with the Bus.
NOTE:- This button is only active in MANUAL mode.
NOTE:- If the bus is live when the manual button is pressed,
synchronising will take place before the load switch is closed.
mode.
CLOSE GENERATOR
This push button is used to control the closure of the generator load
switching device and has two modes of operation :
3. Synchronising is NOT enabled. Pressing this button when the
generator is running off load and in MANUAL mode, the generator load
switch is closed. Further presses of this button will have no effect.
4. Synchronising is enabled. Pressing this button when the generator is
running and in MANUAL mode, the 7510MK1 controller, will volts
match and synchronise with the Bus. The generator load switch is then
closed in parallel with the Bus.
NOTE:- This button is only active in MANUAL mode.
NOTE:- If the bus is live when the manual button is pressed,
synchronising will take place before the load switch is closed.