DSE Model 7560 ATS and Mains Controller Operators Manual
16 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
4.2 TERMINAL DESCRIPTION
4.2.1 DC SUPPLY, FUEL AND START OUTPUTS, OUTPUTS E,F,G
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and
Output relays E,F,G & H
7
Functional Earth
2.5mm²
AWG 13
Connect to a good clean earth point.
8
Output relay E
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
9
Output relay F
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
10
Output relay G
1.0mm²
AWG 18
Plant Supply Positive. from terminal 2. 3 Amp rated.
NOTE:- Terminals 3 to 6 and 11 to 14 are not fitted to the DSE7560 MK1 controller.
NOTE:- Terminals 11 to 30 are not fitted to the DSE7560 MK1 controller.
4.2.2 MSC, MAGNETIC PICKUP, CAN AND EXPANSION
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
MSC
31
MSC H
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
32
MSC L
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
33
MSC SCREEN
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
NOTE:- Terminals 34 to 38 are not fitted to the DSE7560 MK1 controller
NOTE:- Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for
the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable
suitable for MSC use (DSE part number 016-030)