Swgr Shut Down –
Swinger shutdown. After the zone
has reported the programmed number of alarms, the
zone will be shut down. Swinger shutdown is reset
every time the panel is armed, or when the clock
reaches midnight. See Section 10.5 “Swinger Shut-
down.”
Select [Y] to enable this feature. If [N] is selected, the
panel will always transmit when an alarm occurs.
•
TX Delay –
Transmission delay. When the zone goes
into alarm, the panel will sound the bell outputs
immediately but will delay communication to central
station for the programmed amount of time. If the
zone is disarmed before this time expires, no transmis-
sion is sent. If not, the panel will transmit the alarm
after the delay expires.
Select [Y] to enable this feature. If [N] is selected, the
panel will communicate immediately. To program the
Transmission Delay, see Section 10.9 “Transmission
Delay.”
•
Waterflow Del –
This will enable the waterflow delay
for waterflow zones. Waterflow delay operates similar
to transmission delay except both the fire output and
communications will be delayed. If the zone is restored
before the programmable delay time, no transmission
is sent.
Select [Y] to enable this feature. If [N] is selected, the
panel will immediately activate the fire output and
communicate to central station.
Zone 1 Fast Loop Response
If the option Zone 1 Fast (ref # [000200]) is enabled, Zone
1 will have a loop response time of 32ms. If the option is
disabled, Zone 1 will have a normal loop response time
(512ms). The option is disabled by default.