Installing the transmitter
Fitting the sensor
1
Remove bayonet ring from transmitter, remove dummy plate.
2
Open the front cover of the service port with an Allen key by turning anticlockwise
(approx. 60
o
).
3
Only use the DrägerSensor specified on the sticker on the Polytron 3000 measu-
ring unit.
Remove sensor from packaging.
Remove short-circuit jumper from sensor if installed.
There is a coded connector on the back of the sensor. Place the sensor in the
opening with the connector at the back and the Dräger logo at the front.
Before plugging the connector in the socket, ensure that they are identically co-
ded. Incorrect connection can damage the sensor!
Secure sensor in transmitter with bayonet ring.
If the manufacturer's calibration setting for the sensor is to be used:
Open the front cover of the service port with an Allen key by turning anticlockwise
(approx. 60
o
). The maintenance switches and potentiometers for calibration are
now revealed.
4
Jumper J1 must be set over the two left-hand pins or removed completely.
If the transmitter is specifically to be calibrated with calibration gas:
Open the front cover of the service port with an Allen key by turning anticlockwise
(approx. 60
o
). The maintenance switches and potentiometers for calibration are
now revealed.
5
Jumper J1 must be set over the two right-hand pins.
CAUTION
Use only a 5 mm Allen key without a ball head.
00723758_1.eps
1
Polytron
2
00823758_1.eps
Polytron
4
5
3
Summary of Contents for Polytron 3000
Page 25: ...25 ATEX approval ATEX approval ...
Page 26: ...ATEX approval 26 ...
Page 27: ...27 ATEX approval ...
Page 28: ...ATEX approval 28 ...
Page 29: ...29 ATEX approval ...
Page 30: ...ATEX approval 30 ...
Page 31: ...31 ATEX approval ...
Page 32: ...ATEX approval 32 ...
Page 33: ...33 ATEX approval ...
Page 34: ...ATEX approval 34 ...
Page 35: ...35 ATEX approval ...
Page 36: ...ATEX approval 36 ...
Page 37: ...37 ATEX approval ...
Page 38: ...ATEX approval 38 ...
Page 39: ...39 ATEX approval ...
Page 40: ...ATEX approval 40 ...
Page 41: ...41 ATEX approval ...
Page 42: ...ATEX approval 42 ...
Page 43: ...43 ATEX approval ...
Page 44: ...ATEX approval 44 ...
Page 45: ...45 ATEX approval ...
Page 46: ...ATEX approval 46 ...
Page 47: ...47 IECEx approval IECEx approval ...
Page 48: ...IECEx approval 48 ...
Page 49: ...49 IECEx approval ...
Page 50: ...IECEx approval 50 ...
Page 51: ...51 UL approval UL approval ...
Page 52: ...UL approval 52 ...
Page 62: ...Declaration of Conformity 62 Declaration of Conformity ...
Page 63: ...63 Declaration of Conformity ...
Page 64: ...64 ...
Page 65: ...65 Drilling templates Dräger docking station 66 4 mm 02723758_1 eps ...
Page 66: ......
Page 67: ......