Installing the transmitter
8
How to install the electrical connections
— The electrical wiring may be laid and connected only by a qualified electrician,
who must also comply with the appropriate regulations – a screened or uns-
creened cable (such as LiY, LiYCY) may be used.
— Connection to central device with at least 2-wire cable, 0.5 to 2.5 mm
2
.
— For currents of 0 to 22 mA, a DC voltage between 12.0 V DC and 30 V DC must
be present at the transmitter.
Installing the 4 to 20 mA current loop on the transmitter
Fit 2-wire connecting cable in cable gland, cut to length and strip ends
(approx. 80 mm / 3.15").
Shorten the shield (if installed) to prevent short-circuiting:
Connect cable
1
2-pin terminal for Polytron 3000 – check polarity (marking in the docking station).
Cut excess wires short or
2
Fasten in 4-pin terminal.
1
Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station for
future use during commissioning.
Refit raincover (protection against dust and splashing water).
Connecting to the central unit
Connect shield to earth of central unit (e.g. housing, earth bar, etc.).
Connecting the Dräger Polytron 3000 transmitter to a Dräger control unit
(such as Regard, QuadGard, Unigard or Polytron):
— Further information about the connection can be found in the instructions for
the Dräger control unit.
Connecting the Dräger Polytron 3000 transmitter to control units with
a 4 to 20 mA interfaced made by other manufacturers:
— For operation together with control units made by other manufacturers, care
must be taken that the voltage at the transmitter does not drop below 12 V. The
supply voltage, the resistance of the cable and the load and the resistance of any
installed safety barrier must be taken into account.
— Further information about the connection can be found in the instructions for the
control unit being used.
Installing transmitter in mines where firedamp may occur
— Install a safety barrier with the appropriate explosion protection approval
(category M1) between the transmitter and the control unit.
— Only safety barriers or power supply units with the following characteristics may
be used:
U
O
(V
OC
)
≤
30 V, I
O
(I
SC
)
≤
0.3 A, P
O
≤
700 mW.
Make sure the maximum permissible capacitance and inductance connected to the
safety barrier or power supply are not exceeded (taking into account the line as
well). The safety-related input parameters of the transmitter are as follows:
Ci = 0 nF, Li = 50
μ
H.
00323758_1.eps
1
2
Summary of Contents for Polytron 3000
Page 25: ...25 ATEX approval ATEX approval ...
Page 26: ...ATEX approval 26 ...
Page 27: ...27 ATEX approval ...
Page 28: ...ATEX approval 28 ...
Page 29: ...29 ATEX approval ...
Page 30: ...ATEX approval 30 ...
Page 31: ...31 ATEX approval ...
Page 32: ...ATEX approval 32 ...
Page 33: ...33 ATEX approval ...
Page 34: ...ATEX approval 34 ...
Page 35: ...35 ATEX approval ...
Page 36: ...ATEX approval 36 ...
Page 37: ...37 ATEX approval ...
Page 38: ...ATEX approval 38 ...
Page 39: ...39 ATEX approval ...
Page 40: ...ATEX approval 40 ...
Page 41: ...41 ATEX approval ...
Page 42: ...ATEX approval 42 ...
Page 43: ...43 ATEX approval ...
Page 44: ...ATEX approval 44 ...
Page 45: ...45 ATEX approval ...
Page 46: ...ATEX approval 46 ...
Page 47: ...47 IECEx approval IECEx approval ...
Page 48: ...IECEx approval 48 ...
Page 49: ...49 IECEx approval ...
Page 50: ...IECEx approval 50 ...
Page 51: ...51 UL approval UL approval ...
Page 52: ...UL approval 52 ...
Page 62: ...Declaration of Conformity 62 Declaration of Conformity ...
Page 63: ...63 Declaration of Conformity ...
Page 64: ...64 ...
Page 65: ...65 Drilling templates Dräger docking station 66 4 mm 02723758_1 eps ...
Page 66: ......
Page 67: ......