18. Add-on volume based dosing
93
Dr. A. Kuntze
I
Gutes Wasser mit System
Robert-Bosch-Str. 7a
40668 Meerbusch
+49 (0) 2150-7066-0 / Fax -60
www.kuntze.com
18.1. Dosing parameters
In the DOSAGE menu select the symbol DOSAGE. Here you have to
set the following parameters:
Pump output
Define how many liters per hour the pump feeds.
Pulses
Define how many pulses the flow meter gives per liter. This information
allows the instrument to calculate and display the flow rate.
Dosage
Define how many liters of reagent should be dosed per liter of water. Based on this setting and the
pump output the controller calculates how long or how fast the pulses must be to dose the proper
amount of chemicals.