12.1.1 System Alarms Display Map
Display Points
Alarm Point
Description
Solution
11
17
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity of
SNMP trap alarm reporting.
To turn the feature off, set the Timed
Tick timer to 0.
18
Exp. Module
Callout
Alarm is triggered whenever an alarm
point from an Entry Control Unit (ECU)
is collected. A notification event may
be associated with the alarm to force a
call out or trap.
Disable Building Access Control
(BAC) by setting the BAC Unit ID to 0.
If Building Access is being used, then
investigate the ECU alarm source or
don’t associate notification with the
alarm event.
19
Network Time
Server
Communication with Network Time
Server has failed.
Try pinging the Network Time Server’s
IP Address as it is configured. If the
ping test is successful, then check the
port setting and verify the port is not
being blocked on your network.
20
Accumulation
Event
An alarm has been standing for the
time configured under Accum. Timer.
The Accumulation timer enables you
to monitor how long an alarm has
been standing despite system reboots.
Only the user may reset the
accumulated time, a reboot will not.
To turn off the feature, under
Accum.Timer, set the display and
point reference to 0.
21
Duplicate IP
Address
The unit has detected another node
with the same IP Address.
Unplug the LAN cable and contact
your network administrator. Your
network and the unit will most likely
behave incorrectly. After assigning a
correct IP Address, reboot the unit to
clear the System alarm.
22
Battery In Use The unit is running on battery backup
power.
Plug the unit in to commercial power.
23
Low Battery
The internal batteries only have
enough power to operate for approx.
1.5 hours.
Plug in the unit to commercial power.
33
Power Up
The unit has just come-online. The
set alarm condition is followed
immediately by a clear alarm
condition.
Seeing this alarm is normal if the unit
is powering up.
36
Lost
Provisioning
The internal NVRAM may be
damaged. The unit is using default
configuration settings.
Use Web or latest version of NGEdit4
to configure unit. Power cycle to see if
alarm goes away. May require RMA.
Table A3 - System Alarms Descriptions