background image

13

5. Select the following COM port options:

• Connect using COM1 or appropriate COM port
• Bits per second: 9600
• Data bits: 8
• Parity: None
• Stop bits: 1
• Flow control: None

Once connected, you will see a blank, white

HyperTerminal screen. Press Enter to activate the
configuration menu. 

6. When prompted, enter the default password is
dpstelecomNOTE: If you don't receive a password
prompt, check the port you are using on your PC and
make sure you are using the cable provided.

7.  The NetDog 82 BW's main main menu will appear.
Type C for C)onfig, then E for E)thernet. Configure the
unit's IP address, subnet mask, and default gateway.

8. ESC to the main menu. When asked if you'd like to
save your changes, type Y for Y)es. Reboot the NetDog
82 BW to save its new configuration.

Summary of Contents for NetDog 82 BW

Page 1: ...USER MANUAL NetDog 82 BW June 23 2010 D OC UM106 23100 Firmware Version 1 0 Visit our website at www dpstelecom com for the latest PDF manual and FAQs...

Page 2: ...ve work by either mechanical electronic or any other means in whole or in part without prior written consent from DPS Telecom except as required by United States copyright laws The material in this ma...

Page 3: ...82 BW 9 12 via Craft Port 9 1 12 via LAN 9 2 14 GSM GPRS or CDMA Wireless Modem 10 15 TTY Interface 11 16 Menu Shortcut Keys 11 1 16 How to Receive Wireless Alarm Notifications 11 2 17 Monitoring 11...

Page 4: ...ms Display Map 12 1 1 31 Appendix B SNMP Manager Functions 12 2 34 Appendix C SNMP Granular Trap Packets 12 3 36 Appendix D ASCII Conversion 12 4 37 Technical Support 13 38 Frequently Asked Questions...

Page 5: ...1 internal 1 external Built in Web Browser interface for config and monitoring 24 7 pager and email alerts no master needed Reports to multiple SNMP managers and T Mon NOC simultaneously SNMP and or...

Page 6: ...nterface Shipping List 3 While unpacking the NetDog please make sure that all of the following items are included If some parts are missing or if you ever need to order new parts please refer to the p...

Page 7: ...video security surveillance of remote sites The SiteCAM connects to a separate 10 100BaseT hub SiteCAM video can be accessed directly from the NetDog s Web Browser Interface Up to four cameras can be...

Page 8: ...DCPx TRIP HTTP Interfaces 1 DB9 RS232 Craft Port 1 RJ45 10BaseT Ethernet port 2 5mm stereo jack for optional external temperature sensor 24 screw down connectors and blocks 28 in the 4 analogs version...

Page 9: ...following tools Phillips No 2 Screwdriver Small Standard No 2 Screwdriver Wire Strippers Cutter PC with terminal program i e HyperTerminal NOTE To install the NetDog in one of the wall mount configura...

Page 10: ...screws longer than those provided may contact the internal components of the NetDog adversely affecting normal operation 3 After flanges have been attached to the NetDog mount it in the appropriate lo...

Page 11: ...he fuse until all connections to the unit have been made 2 Remove the power connector plug from the Power Connector Note that the plug can be inserted into the power connector only one way this ensure...

Page 12: ...ernal battery pack s disconnected To plug in the battery packs for the first time or to change the batteries follow these simple steps These instructions assume the NetDog is facing you as shown below...

Page 13: ...front panel Alarm and Control Relay Connections 8 1 Fig 8 2 Alarm and control relay connectors The NetDog s discrete alarm inputs control relay outputs and optional analog alarm inputs and fuse alarm...

Page 14: ...he circuit board Example If connecting alarm points to a dry contact relay look at the dry contact example Be sure to set jumpers A and C then bring out the leads from 1A and 1B to both contacts of th...

Page 15: ...latched Alarms 1 8 Solid Red Associated alarm is in alarm state Wireless Blink Green Transmit to wireless Blink Red Receive from wireless Craft Blink Green Transmit over craft port Blink Red Receive o...

Page 16: ...physical cable connection between your PC s COM port and the unit s craft port Note You must be connected via craft port or Telnet to use the TTY interface Make sure you are using the straight through...

Page 17: ...en prompted enter the default password is dpstelecom NOTE If you don t receive a password prompt check the port you are using on your PC and make sure you are using the cable provided 7 The NetDog 82...

Page 18: ...ill temporarily change your PC s IP address and subnet mask to match the NetDog s factory default IP settings Follow these steps 1 Get a LAN crossover cable and plug it directly into the NetDog 82 BW...

Page 19: ...the same 48 VDC power as the NetDog which provides more secure more robust operation than modems that run off commercial power You may use any service provider you choose for your wireless connectivi...

Page 20: ...anel craft port or a remote connection via Telnet Some initial software configuration must be performed before you can use a remote connection to the NetDog For Telnet connect to the NetDog s IP addre...

Page 21: ...cted DPS Telecom recommends CrossBridge Solutions and will be using this provider in the example 2 Access the TTY interface for the NetDog 82 BW using terminal emulating software on your PC Logon to t...

Page 22: ...nDemand Unit will communicate via wireless when LAN is unavailable but only when an alarm occurs that needs to be reported This setting is recommended because it conserves bandwidth 4 After selecting...

Page 23: ...owser User Manual on the Resource Disk In the Edit Menu Timers enter the number of minutes before you want to PPP connection to timeout after an event 7 Now let s setup SNMP traps to be reported over...

Page 24: ...the second image is the designated IP address we need 9 From the Web Browser interface go to Edit SNMP Enter IP address from Step 8 in the IPA field and Save 10 If you experience problems receiving an...

Page 25: ...oring of the NetDog including all alarms ping information relays analogs and system status Fig 11 2 The monitor menu allows status checking on all elements 11 3 1 1 Monitoring Base Alarms View the sta...

Page 26: ...n and IP address Under Status the word Alarm will appear if an alarm has been activated and Clear will appear if an alarm condition is not present Fig 11 4 The Ping info submenu allows you to change p...

Page 27: ...default If your sensor s output is current change the appropriate analog shunt to the current measuring position The scaling worksheet in the provisioning section converts all readings shown here into...

Page 28: ...vent system alarm Refer to the figure and table below to define the accumulation timer Fig 11 8 Monitor and reset the Accumulator Timer Field Description Display and Point Reference Indicates which al...

Page 29: ...ping table 11 3 3 Proxy Menu You can create proxy connections to reach through to the craft port or modem port from the P roxy menu You ll be able to monitor and control additional devices via proxy c...

Page 30: ...a via FTP 1 From the Start menu on your PC select RUN 2 Type ftp followed by the IP address of the NetDog you are backing up e g ftp 126 10 120 199 3 After the connection is made press Enter 4 Enter t...

Page 31: ...nter the password of the NetDog default password is dpstelecom then press ENTER 5 Type binary and press Enter necessary for NetDog file transfer 6 Type lcd and press Enter this allows you to change th...

Page 32: ...Shows hardware access operation i 14 PING toggle switch k 15 Socket toggle switch Shows current dcu resources l 16 LED toggle switch Shows current LED state L 17 LCD display toggle switch Shows LCD c...

Page 33: ...4 99 1 13 NetDog 82 BW Expansion 1 Relays 1 8 or NetDog 82 BW 480 as DX Relays 1 4 6065 6072 7065 7072 99 1 13 NetDog 82 BW 480 as DX Alarms 65 80 6081 6096 7081 7096 99 1 14 NetDog 82 BW Expansion 2...

Page 34: ...not Sent 8683 9683 44 Pager Que Overflow 8684 9684 45 Notification failed 8685 9685 46 Craft RcvQ full 8686 9686 47 Modem RcvQ full 8687 9687 48 Serial 1 RcvQ full 8688 9688 49 Serial 2 RcvQ full 8689...

Page 35: ...Accumulation timer enables you to monitor how long an alarm has been standing despite system reboots Only the user may reset the accumulated time a reboot will not To turn off the feature under Accum...

Page 36: ...event occurred Define the IP Address where you would like to send SNMP trap events or configure the event not to trap 44 Pager Queue Overflow Over 250 events are currently queued in the pager queued...

Page 37: ...GLD communication bus 61 GLD 3 fail One or more GLD units addressed 3 through 12 may be failed Reduce the number of connected GLD units to determine which unit may be causing the link to fail 62 Chan...

Page 38: ...ontrol Grid 3 the Display 3 Tbl B1 O _OV_Traps points _OV_vTraps 1 3 6 1 4 1 2682 1 4 0 PointSet 20 PointClr 21 SumPSet 101 SumPClr 102 ComFailed 103 ComRestored 014 P0001Set 10001 through P0064Set 10...

Page 39: ...99 1 11 1 8 Undefined 99 1 11 9 16 Timed Tick 99 1 11 17 Exp Module Callout 99 1 11 18 Network Time Server 99 1 11 19 Undefined 99 1 11 20 Duplicate IP Address 99 1 11 21 Undefined 99 1 11 22 32 Power...

Page 40: ...0xBAB0 Checksum Table C 1 UDP Headers and descriptions SNMP Header Description 0 Version Public Request Trap Request 1 3 6 1 4 1 2682 1 4 Enterprise 126 10 230 181 Agent address Enterprise Specific G...

Page 41: ...l surrounded by brackets e g IF A received BREAK will appear as BRK Abbreviation Description Abbreviation Description NUL Null DLE Data Link Escape SOH Start of Heading DC Device Control STX Start of...

Page 42: ...rmation when you call our Technical Support representatives can assist you in gathering it Please write the information down for easy access Please have your user manual and hardware serial number rea...

Page 43: ...ardware in most terminal programs and this will not work correctly with the NetDog Q I can t change the craft port baud rate A If you select a higher baud rate you must set your terminal emulator prog...

Page 44: ...your NetDog Ordering TTL points for your NetDog does not add to the cost of the unit What you can do with the configuration software is change any alarm point from Normal to Reversed operation Switchi...

Page 45: ...SNMP manager A The control relays are operated by issuing the appropriate set commands which are contained in the DPS Telecom MIB For more information about the set commands see Appendix Display Mappi...

Page 46: ...assign the NetDog an e mail address choose System from the Edit menu Enter the NetDog s user name in the Name field it can t include any spaces and the domain in the Location field For example if the...

Page 47: ...43...

Page 48: ...rm Management Dependable Powerful Solutions that allow users to monitor larger more complicated networks with a smaller less trained staff www dpstelecom com 4955 E Yale Fresno CA 93727 559 454 1600 8...

Reviews: