The NetDog's two relays can be operated from this screen
11.3.1.4 Monitoring Analogs
View the current reading and the alarm status of your analog devices from the M)onitor menu > a(N)alogs
option. The value shown is a snapshot of the channels measurement, not a real-time reading. Refresh the readings
by re-selecting the analogs option. Alarm status indicates that a preset threshold has been crossed and is
designated by an
x
.
The four analog measuring inputs are set to measure voltage as the factory default. If your sensor's output is
current, change the appropriate analog shunt to the current measuring position. The scaling worksheet in the
provisioning section converts all readings shown here into native units, such as degrees Celsius or percent
relative humidity.
Fig. 11.6 -
This display allows you to monitor the NetDog's 4 analog inputs
11.3.1.5 Monitoring System Alarms
View the status of the NetDog's system alarms from the M)onitor menu > S)ystem option. Under
Status
, the
word
Alarm
will appear if an alarm has been activated and
Clear
will appear if an alarm condition is not
present. See Appendix, "System Alarm Descriptions," for more information. If groups are used the user defined
status will be displayed.