32
Display Points
Alarm Point
Description
Solution
11
37
DCP Poller
Inactive
The unit has not seen a poll from the
Master for the time specified by the
DCP Timer setting.
If DCP responder is not being used,
then set the DCP Unit ID to 0.
Otherwise, try increasing the DCP
timer setting under timers, or check
how long it takes to cycle through the
current polling chain on the Master
system.
38
NET1 not
active
The Net1 LAN port is down.
Check LAN cable. Ping to and from
the unit.
39
NET2 not
active
The Net2 LAN port is down.
40
LNK Alarm
No network connection detected
41
Modem not
responding
An error has been detected during
modem initialization. The modem did
not respond to the initialization string.
Remove configured modem
initialization string, then power cycle
the unit. If alarm persists, try resetting
the Modem port from the TTY
interface, or contact DPS for possible
RMA.
42
No Dial Tone
During dial-out attempt, the unit did
not detect a dial tone.
Check the integrity of the phone line
and cable.
43
SNMP Trap
not Sent
SNMP trap address is not defined and
an SNMP trap event occurred.
Define the IP Address where you
would like to send SNMP trap events,
or configure the event not to trap.
44
Pager Queue
Overflow
Over 250 events are currently queued
in the pager queued and are still trying
to report.
Check for failed notification events
that may be filling up the pager queue.
There may be a configuration or
communication problem with the
notification events.
45
Notification
failed
A notification event, like a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
46
Craft RcvQ full
The Craft port received more data
than it was able to process.
Disconnect whatever device is
connected to the craft serial port. This
alarm should not occur.
47
Modem RcvQ
full
The modem port received more data
than it was able to process.
Check what is connecting to the
NetDog 82 BW. This alarm should not
occur.
48
Serial 1 RcvQ
full
Serial port 1 (or appropriate serial port
number) receiver filled with 8 K of data
(4 K if BAC active).
Check proxy connection. The serial
port data may not be getting collected
as expected.
49
Serial 2 RcvQ
full
50
Serial 3 RcvQ
full
51
Serial 4 RcvQ
full
52
Serial 5 RcvQ
full
53
Serial 6 RcvQ
full
54
Serial 7 RcvQ
full
55
Serial 8 RcvQ
full
Table A3 - System Alarms Descriptions (continued)
Summary of Contents for NetDog 82 BW