FIRE DOOR WIRING
When the ED 800 is installed on a fire door, the main power to the unit must be supplied through a
set of contacts in a UL listed fire alarm panel. The contacts are to be closed under normal
(stand-by) conditions providing power to the unit. Under alarm conditions, the contacts must open,
cutting power to the unit, causing the ED 800 to operate as a manual door closer.
SPST SWITCH
RATED @
3amp @ 120 VOLTS MIN.
(BY OTHERS)
HOLD OPEN
CLOSE
OFF "0"
ON "1"
REMOTE SWITCH OPTION (refer to Installation Instructions 08105680)
If the ED 800 is ordered with the RS - Remote Switch option, the On/Off switch and the Hold
Open/Close switch are deleted. This is recommended for applications where the switches may be
subjected to tampering. In this application, a remote switch must be provided (by others) in the
incoming power supply. This switch must be wired in accordance to The National Electrical Code.
FUSE
The ED 800 is protected by a 3 amp type AGC size 1/4" x 1 1/4" fuse. Replace only with an
identical fuse.
WARNING: DISCONNECT POWER TO THE ED 800 WHEN REPLACING THE FUSE.
ON/OFF SWITCH
The ED 800 is equipped with an on/off switch which is located in the end cap closest to the control
module. The switch must be in the "on" position for any powered function. It is recommended that
the switch be in the "off" position after hours or during extended idle periods.
HOLD OPEN/CLOSE SWITCH
The ED 800 is equipped with a standard "hold open" feature. To activate, momentarily depress the
switch towards "hold open". The door will open and remain in the open position for approximately 5
minutes. After that period of time, the door will then close and the unit will be ready for normal
operation. To close the door at any time, depress the switch towards "close". This will override the
time delay and close the door immediately.
NOTE: Hold Open/Close Switch must be plugged into control module to enable operator.
08102710 05/07
ED800-15