background image

GENERAL INFORMATION

Functional Detail

The DORMA ED 800 low energy power operator was designed 
to make doors accessible, while still providing the good 
operating characteristics of a manual door closer.

The ED 800 is based on the DORMA TS83 door closer and 
offers the same sweep, latch, backcheck, adjustable spring 
power and operating efficiencies.  In the normal mode of 
operation, the ED 800 will be used as a manual door closer.  
Upon activation the unit will open the door, hold the door open 
for a predetermined period, and close the door under the 
parameters as set forth by ANSI A156.19, Standard for 
Power Assist and Low Energy Power Operated Doors.

The mechanical components of the unit consist of a 
permanent magnet type DC motor,  which drives a lead screw 
assembly.  The lead screw assembly has a recirculating ball 
nut with a shuttle attached to it.  The shuttle drives the TS83 
door closer.

The electronic components of the unit consist of the motor, 
an encoder assembly, a control module, a power transformer, 
and additional electronic components and assemblies.  The 
transformer is powered by line voltage. The transformer 
powers the control module.  The motor is driven by the  
control module.  The motor shaft turns an incremental 
encoder which indicates the motor velocity to the control 
module.  The control module responds to external inputs such 
as an activation switch and internal door inputs such as an 
obstacle encountered in the opening or closing cycle.

The unit also provides a manual rocker switch for a hold 
open function.  The hold open switch will override all other 
inputs, and will hold the door open approximately 5 minutes.  
After that period of time, the door will automatically close and 
return to the automatic mode.  The door can also be closed at 
any time by pushing the hold open rocker switch in the 
opposite direction.

The ED 800 has two basic functions which can be selected in 
the field:  Low Energy or Power Assist. The factory setting will 
be at Low Energy. In the Low Energy function, when the 
door is activated, the door will open within the speed and 
force guidelines,  per ANSI A156.19.  The door will open to a 
position which is adjustable between 85° and 115°, and will 
stay in the hold open position for a period of time which is 
adjustable from 5 to 60 seconds.  At the expiration of the 
selected time, the door will begin to close.  The time delay 
commences once the door attains the fully open position, or 
when it last receives an actuation input, whichever occurs 
later.

In the opening cycle the door will exert a maximum of 15 lbf. 
at the latch edge of the door.  In the event an obstacle is 
encountered, the power will be reduced to the door, so that 
the door is held in a balanced state.  

While in the balanced state the door can easily be pushed open 
or closed, as needed.  The door will remain in the balanced state 
for the length of time as set by the time delay adjustment.  The 
time delay commences once there is no longer any door 
movement.

In the closing cycle a maximum of 15 lbf. may be generated at 
the latch edge of the door.  If an obstacle is encountered,  the 
unit will balance the door.  While in this state the door can easily 
be pushed open or closed manually, as needed.  The door will 
remain in the balanced state for the length of time as set by the 
time delay adjustment. The time delay commences once there is 
no longer any door movement.

If at any time there is a power failure, the unit will operate as a 
standard TS83 door closer.

The second basic function is power assist.  When the power 
assist is activated, the unit responds by opening the door 
approximately one inch, to alert the user that the power assist 
mode is active.  The door can then be opened with a reduced 
opening force, which can be adjusted from 1/2 lb. to 5 lbs., as 
measured from the latch edge of the door.  The reduction of 
opening force remains active as long as the unit senses door 
movement, plus the duration of the time delay setting.  The time 
delay will commence after there is no door movement.  At the 
expiration of the time delay, the door begins to close under the 
control of the TS83 door closer.

When the ED 800 is initially energized, it will perform a learn 
cycle. If the door is latched and can not open during the learn 
cycle, the ED 800 will default to the power requirements of a 
typical 36" wide interior door. If an electric strike, magnetic lock 
or electric latch retraction device is installed and tied in with the 
delay contacts, the ED800 will automatically send a signal to 
unlock the strike, magnetic lock or hold back the electric latch. 
The ED800 will only go through a full learn cycle when turned on 
at the ON/OFF switch. During the learn cycle, the exact closed 
position of the door will be established.  Also, the ED800 will  
open the door a few degrees to determine the amount of force 
required to compress the door closer spring and set the door in 
motion.  From this information, along with the "door width" 
setting, the control module can determine the amount of force to 
exert on the door so as not to exceed the 15 lbf. maximum 
required by the ANSI 156.19 standard. If the ED800 losses 
power, (other than the ON/OFF switch) when power is restored 
the ED800 does a Secure Learn. The most recent learn cycle is 
stored in memory and is used so that the door stays secure 
(locked and latched) during and after a power failure.

Activation of the ED 800 can be by any normally open circuit 
which is momentarily closed to signal the door.  The most basic 
means of activating the unit would be a wall switch or frame 
switch which is directly wired to the external connector.  A radio 
frequency receiver along with a radio frequency wall switch 
transmitter, or hand held transmitter, can be used if it is 
considered too difficult to run wires from the push button to the 
unit.  For doors that are specifically dedicated for accessibility, a 
motion sensor is available to activate the unit.  Keep in mind that 
when the unit is not activated it will operate as a standard TS83 
door closer.

ED800-4

08102710    05/07

Summary of Contents for ED800 J

Page 1: ...DORMA ED800 SERIES 08102710 05 07 www dorma usa com 1 800 523 8483 ED800 T ED800 J INSTALLATION INSTRUCTIONS...

Page 2: ...itch Option 15 Fire Door Wiring 15 Power Adjustments Push Pull Switch 16 Latch Delay On Off Switch 16 Low Energy Function 16 Power Assist Function 17 Latched Door 17 ED800 Controller Module Diagram 18...

Page 3: ...ors and accessories 1 Long No 2 Phillips screwdriver 2 No 3 Phillips screwdriver 3 1 8 blade screwdriver 4 3 16 blade screwdriver 5 Tape measure 6 10 Adjustable wrench 7 Center punch 8 Hammer 9 5mm He...

Page 4: ...delay commences once there is no longer any door movement In the closing cycle a maximum of 15 lbf may be generated at the latch edge of the door If an obstacle is encountered the unit will balance th...

Page 5: ...an obstacle within the swing area of the door In addition the unit will hold the door in the fully opened position until traffic has cleared from the swing area of the door Under no circumstances how...

Page 6: ...ME FOR PLATE FOR 1 4 20 MACHINE SCREWS USE No 7 0 201 DRILL FOR No 14 WOOD SCREWS USE 5 32 DRILL FOR SEX NUTS USE 3 8 DRILL TWO 2 HOLES IN DOOR FOR ARM SHOE 8 13 16 1 3 4 SEE NOTE 5 2 TO 6 STD 3 1 4 8...

Page 7: ...ew in connecting arm so arm slides freely Adjust connecting arm length so rod and connecting arm are 90 to door Re tighten screw 08102710 05 07 ED800 7 Initially install screws for slots A as pictured...

Page 8: ...2 HOLES IN DOOR FOR ARM SHOE 8 13 16 1 3 4 SEE NOTE 5 2 TO 6 STD 3 1 4 83 3 15 16 100 7 8 DIA HOLE FOR WIRE ACCESS 15 16 MINIMUM TO CEILING 1 3 4 1 5 16 33 12 5 8 321 525 20 11 16 4 3 8 111 11 16 17 6...

Page 9: ...Tighten all screws securely 08102710 05 07 Remove two 2 cover screws and cover Disconnect cover ground wire at base plate Loosen but do not remove end cap screws and slide end caps off Note Re instal...

Page 10: ...oe drop plate Place wrench on top pinion shaft and rotate pinion slightly toward latch edge of door Slide main arm over bottom pinion shaft Fasten securely with pinion screw and lock washer provided L...

Page 11: ...ed COVER END CAP END CAP WITH SWITCHES GROUND WIRE FOR COVER END CAP SCREW LEFT HAND MOUNT SHOWN 100 1 2 597 13 21 13 16 3 RIGHT HAND DOOR SHOWN BOTTOM OF FRAME NOTES C OF HINGE 1 DO NOT SCALE DRAWING...

Page 12: ...ided 08102710 05 07 ED800 12 Initially install screws for slots A as pictured allowing 5 16 between the screw head and the frame Align the slots in the mounting plate with the screws Slide the mountin...

Page 13: ...JUSTMENT Adjust spring tension according to the chart below The ED 800 is shipped from the factory as a size 3 The spring power can be increased to a size 5 Clockwise turns increase spring power Do no...

Page 14: ...power cord to the receptacle do not run through doorways window openings walls ceilings floors or the like Do not attach or otherwise secure the power cord to the building structure and do not conceal...

Page 15: ...nce to The National Electrical Code FUSE The ED 800 is protected by a 3 amp type AGC size 1 4 x 1 1 4 fuse Replace only with an identical fuse WARNING DISCONNECT POWER TO THE ED 800 WHEN REPLACING THE...

Page 16: ...when the door is in the hold open position 5 Adjust the Delay Time potentiometer to obtain the desired amount of time the door will remain at the hold open position This is adjustable from 5 to 60 se...

Page 17: ...le holding the latch retracted until the learn cycle is completed POWER ASSIST FUNCTION 1 Adjust the Power Assist Low Energy slide switch to the Power Assist position 2 Adjust the Door Width potentiom...

Page 18: ...use only Hold Open Switch Connection Closing Obstacle Switch Off On Mount Style Switch Push Pull Latch Delay Switch Off On External Connector NOTE Terminal can be removed from control module to simpl...

Page 19: ...external connector Note Accessory wires must be isolated from 120V incoming power ACCESSORY WIRE ROUTING Remove knockout with a 1 2 diameter punch and hammer Back side of end cap must be supported to...

Page 20: ...allow for the door to open FS 1 FRAME SWITCH The FS 1 Frame Switch is designed to be installed in a metal door frame with a minimum width of 1 3 4 NOTE Generally a junction box is not used with this t...

Page 21: ...hes numbered 1 through 10 located on the receiver board To gain access to the switch remove the top section of the case Any combination of on closed or off open positions can be selected by using a sm...

Page 22: ...s weak or dead and should be replaced After installation is complete check for proper operation KC RFT 1 Transmitter and KC RFT 2 Transmitter The KC RFT key chain transmitters are used in conjunction...

Page 23: ...cause both doors to open at the same time ED800 23 08102710 05 07 SEQUENTIAL OPERATION SINGLE DOORS In this operation the doors will open in sequence The switch at each door will activate that door Af...

Page 24: ...0 provides a normally open set of contacts which close momentarily to act as a switch to signal the power supply for the latch retraction When activated the contacts close immediately and stay closed...

Page 25: ...A ADJUSTMENT DELAY FIRE 1 2 CONTACT DRY 3 4 5 INPUT OUTPUT B 120 VAC DIP SWITCH OUTPUT A 8 DRY CONTACT 6 7 OFF ON INPUT POWER TRANSFER EXIT DEVICE Typical wiring diagram for the ED800 with PS501 Power...

Page 26: ......

Page 27: ...02710 05 07 ED800 27 ED 800J x 870 ANGLE BRACKET TOP JAMB INSTALLATION TEMPLATE ED 800J x 870 ANGLE BRACKET x 831 ARM SHOE DROP PLATE TOP JAMB INSTALLATION TEMPLATE 1 1 4 44 32 3 LEFT HAND DOOR SHOWN...

Page 28: ...smitter Type Frequency Range Numbers of Codes Battery Type ED800 28 08102710 05 07 120 Volts AC 10 15 50 60 Hz 2 Amp 3 Amp type AGC size 1 4 x 1 1 4 12 Volts nominal filtered unregulated Range 10 to 2...

Reviews: