POWER CORD OPTION (refer to Installation Instructions 08076325)
The ED800 is available with an optional power cord which allows the unit to be plugged directly
into a standard receptacle. If power cord is being added as a field option, refer to instructions
packaged with power cord. A grounding-type 120 volt receptacle rated for a minimum of 15 amps.
is required and should be located at the approximate location shown. When considering the
amount of units to be supplied by one circuit, remember the power consumption is 2 amps. per
unit.
When routing the power cord to the receptacle, do not run through doorways, window openings,
walls, ceilings, floors, or the like. Do not attach or otherwise secure the power cord to the building
structure, and do not conceal the power cord behind walls.
WARNING: DO NOT ALLOW THE POWER CORD TO BECOME ENTRAPPED IN THE MOVING
PARTS OF THE ED 800 OR THE DOOR AND THE FRAME.
If the local codes require permanent wiring to be employed, refer to Main Power Connection
section.
MAIN POWER CONNECTION
Connect the 120 volt AC power supply wires to the ED 800 terminal block. Connect the ground
wire to the green ground screw on the mounting plate. Observe all local electrical codes when
performing connections.
The incoming wire size is to be 14 AWG. The maximum power consumption of the ED 800 is 2
amps.
WARNING: DISCONNECT POWER WHILE MAKING CONNECTIONS.
08102710 05/07