F04 (lock out error)
Three unsuccessful
ignition attempts.
No gas
1. Open the main gas supply valve and/or the manual gas supply
valve before the gas control valve
2. Check supply pressure to the gas control valve
3. If necessary, restore the gas supply
To restore the gas supply, contact your installation engineer
Air in the gas pipes
Bleed the air out of the gas pipe
(3.11 "Checking supply pressure,
CO
2
value and switching pressure")
See
Checking supply pressure, CO
2
value and switching pressure
for how to bleed air from the gas line, and how to measure the
supply pressure and burner pressure.
To replace the necessary parts, you must contact your installation
engineer
Defect in the hot
surface igniter circuit
1. Check that the hot surface igniter is correctly connected (JP2).
2. Check the wiring of the hot surface igniter.
3. Measure the resistance across the hot surface igniter. This must
lie between 2 and 10 Ohm (at room temperature).
4. Check that the hot surface igniter lights up during ignition.
5. If necessary, replace the hot surface igniter.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Defect in the ionisation
circuit
1. Check that the flame probe is correctly connected (JP2)
2. Check the wiring of the flame probe
3. Measure the ionisation current. This must be a minimum of
1.5 microA.
4. If necessary, replace the wiring.
Supply voltage too low Check the supply voltage, this must be 230 V
AC
(-15%, +10%)
F05 (lock out error)
Too many flame errors
have been signalled.
Incorrect roof or wall
flue terminal.
Recirculating flue
gases.
1. Check that the correct roof or wall flue terminal has been
installed
(3.9 "Air supply and chimney flue discharge")
.
2. If necessary, install the correct roof or wall flue terminal.
3. Check that the roof or wall flue terminal discharges into a
permitted area.
If the error cannot be resolved or is persistent, contact your
installation engineer
Code + description
Cause
Measure
Remark
Summary of Contents for DR-FC 120
Page 2: ......
Page 4: ......
Page 6: ...4 Instruction manual DR FC gis...
Page 10: ...Table of contents 8 Instruction manual DR FC...
Page 58: ...Shutting down 56 Instruction manual DR FC 10 gis...
Page 70: ...Service program 68 Instruction manual DR FC 12 is...
Page 84: ...Service interval 82 Instruction manual DR FC 14 is...
Page 90: ...Warranty 88 Instruction manual DR FC 16 s...
Page 93: ...Instruction manual DR FC 91 is...
Page 96: ...Appendices 94 Instruction manual DR FC 17 is...
Page 98: ...Instruction manual DR FC 96...