Installation
40
Instruction manual DR-FC
3
is
10. Read the pressure from the meter at the moment when the water heater
switches from
PRE PURGE
to
PRESSURE SWITCH
. At this point, the
water heater's display will show:
11. Check whether the measured value matches the value from the
table
(3.4.3 "Gas data")
.
Note
If the
PRESSURE SWITCH
message does not appear, there is a fault. This
must be resolved first by a qualified service engineer.
12. Shut off the gas supply.
13. Disconnect the pressure gauge.
14. Put the two black caps back on the pressure switch.
15. Replace the covers.
ON
Ê Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
PRESSURE SWITCH
a