CellCom‑LTE Programming and Installation Guide
6
APPLICATIONS
The communicator can be used in a variety of applications.
CID Dialer Connection
Directly connect one or both tip and ring terminals from the control panel to the communicator. See Figure 4. This
connection captures Contact ID messages from any fire panel that are based on the SIA communication standard
DC‑05‑1999.09‑DCS. Messages are then formatted into a Serial 3 message and sent to an SCS‑1R Receiver or SCS‑VR
Receiver.
Note:
CID Dialer Connection cannot be used when using Zone 4 Bell Connection. Do not connect telephone
company wires to the communicator. Remove any connected telephone company wires from the control panel.
Communication Failure (CellComF only)
The phone line voltage on the second tip and ring will drop when the CellComF‑LTE is in a communication failure
state. This triggers the host panel to annunciate a communication failure. When communication is restored, voltage is
restored on the second tip and ring terminal and the host panel sees a restoral on the phone line.
Zones 1-4 Input Connection
Connect each control panel relay output to a zone on the communicator. For programming purposes, the zone
numbers are 1‑4. The following are examples of how you might use this application for a burglary or fire alarm.
Burglary
Use a normally closed output on a burglary control panel to indicate a burglary alarm. The communicator zone should
be programmed with a zone name and burglary zone type. When the output on the control panel turns on and trips
the communicator zone, a message is sent to an SCS‑1R or SCS‑VR receiver at the central station. The zone name
programming can be used to describe which control panel zone indicated a burglary. See Figure 5.
Note:
Zone 4 can only be used as a standard input zone when not programmed as zone type Auxiliary 2 (A2). See
Figure 4: Wiring Diagram for Tip and Ring Connection
Use 18-22 AWG
for Power Supply
connection
CellComF-LTE-V
+DC- Z1 Z2 Z3 G
T1 R1 T2
+Z4-
R2
O1 O2
+
–
Tip 1
Ring 1
12/24 VDC Aux. Output
+
-
Ground
Control Panel
The panel or separate power
supply must be listed for fire,
regulated, and power limited.
Telephone
Jack
Connector
BELL -
BELL +
Tip 2 Ring 2
Telephone
Jack
Connector
No Connection
(Zone Inputs Not
Evaluated By UL)
Wiring to FACP shall be connected within 20 ft in the same room and routed in conduit.
If FACP only has one phone line, connect to T2, R2
+DC- Z1 Z2 Z3 G
T R
+Z4- O1 O2
Use 18-22 AWG for
Power Supply connection
Z3 +
Z4 +
Z4 -
GND
Aux. Output
+
-
Ground
Control Panel
The panel or separate power
supply must be 12/24 Volt
Regulated and Power Limited.
Z1 +
+
–
Z2 +
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
1k ohm
1k ohm
1k ohm
1k ohm
Figure 5: Wiring Diagram for Burglary Zones 1-4