11. Calculation EEPROM cam storage
In the CamCon you have the opportunity to extend the
EEPROM
Cam storage. The storage space
required for programming is influenced by the following factors:
1. Basic requirement
= 256 Bytes
2. Per cam
= 12 Bytes
3. Per set delay time for Speed Compensation = 12 Bytes
4. Per name for an output
= 24 Bytes
5. Per set key / code
= 66 Bytes
6. For a special measuring system
= 66 Bytes
7. For direct or ”actual” program selection
= 12 Bytes
8. Per set program name
= 48 Bytes
9. Per line of the OP function
= 72 Bytes
The value is generated by the CamCon with the following formula:
Storage requirements in Bytes
=
Basic needs
+
Number of cams * 12
+
Number of delay times for Speed Compensation * 12
+
Number of output names * 24
+
Number of user keys * 66
+
66 when the special measuring system is available.
+
12 when "on Pos" program selection is set.
+
48 * number of set program names.
+
72 * number of set lines of the OP function.
Example 1:
The Cam Switch Unit is supposed to have 8 Programs each with 16 cams and Speed
Compensation for 16 outputs.
Storage requirement in Bytes = 256 Bytes + ( 8 Programs * 16 * 12 Bytes ) + ( 16 * 12 Bytes )
Storage requirement = 1984 Bytes
Example 2:
The Cam Switch Unit is supposed to have 20 programs each with 16 cams and 16
delay times for Speed Compensation.
Storage requirement in Bytes
=
256 Bytes
+
( 20 Programs * 16 * 12 Bytes )
+
( 16 TZK * 12 Bytes )
+
( 16 Output names * 24 Bytes )
+
( 1 User keys * 66 Bytes )
Storage requirement = 4738 Bytes
Warning:
Through alterations in the storage structure of the CamCon software, the extent to
which storage capacity is used up can differ from software version to software version!
,Version from: Aug. 04