Digitronic
Digital Cam Switch Unit
Automationsanlagen GmbH
CamCon DC50/51
9.8. Problem: The EEProm memory is full.
Cause:
Too little memory space available in the EEPROM for the storage process.
Solution:
Please contact your customer service representative if you require an EEProm storage extension.
Also consult Chapter "11. Calculation EEPROM cam storage on page 84.
9.9. Problem: Outputs will not activate
Possible causes:
An error message is active. The outputs are not connected to power supply. A programed Cam is to
short or gets to short by increasing rotation speed. The enable - Input is not set.
Solution:
Check the error message.Program a longer Cam. A Cam with delay-time/speed-compensation must at
least have the length of two steps.
Enable Outputs at the enable-Input, see also chapter 7.4.6.6. Input for enableling Outputs on page 63
Enable the outputs through the S5 PLC. Consult your handbook for the S5-L1 linkage.
9.10. Problem: "Out - Error".
Possible causes:
Your outputs are overloaded or short-circuited. Check the wiring and the connection output as well as
possible inductive loads which have no zero setting or are driven by a cancellation component.
The number of set inputs is not correct.
Power failure at an external interface module (e.g. DC91/IO or DC16/IO).
Solution:
See chapter "4.3. The outputs" on page 24.
See chapter "7.4.6. System upgrading" on page 63.
See chapter "7.5.6. Configure Hardware" on page 75.
If the error is eliminated, the error-message can be deleted by pressing
Here the attempt to reset outputs is done
Warning:
Wires crossing behind the
outputs, if the cables leading towards the switch-
OFF of the outputs are in an awkward position, can lead to a switch-OFF of the
outputs, since in an open situation a potential is built up which, when the
contacts are closed, is led back into the outputs.
In inductive loads the outputs must be organised with a flywheeling diode. Protection or
induction in the switch cabinet in the immediate vicinity of the device or due to their wiring
have an effect on the device or its wiring and must be organised with cancellation
components.
9.11. Problem: Error in the EEPROM.
Possible causes:
The data of the EEPROM was changed or destroyed by interference.
One of the existing data carriers (EEPROM or EPROM) was renewed or is defective.
The power supply was switched OFF during alteration of the data.
Solution:
Press
for yes and then the
key. All data will be erased and must be re-entered.
Should these errors occur repeatedly, please contact your customer service.
9.12. Problem: "Error ???"
Possible causes:
An unpredictable error has occurred.
Solution:
Please contact your customer service.
,Version from: Aug. 04
Page: 81
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com