Digitronic
Digital Cam Switch Unit
Automationsanlagen GmbH
CamCon DC50/51
9.13. Problem: "Clear...."
Cause:
The CamCon is waiting for the arrival of the Clear signal in an incremental measuring system.
Solution:
Set the Clear signal ON or activate an actual value Preset. The result is the immediate release of the
Cam Switch Unit.
Note:
The incremental measuring system is only available as an option for CamCon DC16,
DC50/51, DC115, DC300 and CamCon 1756-DICAM.
See chapter "7.4.1.6.3. Incremental - measuring system" on page 49.
,Version from: Aug. 04
Page: 82