DGM INSTALLATION AND MAINTENANCE MANUAL
34
700135-0000 Rev. O
The passnumber you entered does not give you access to this
function. Press CLR/SIL to clear display or FUNC to view next
Function.
Enter the four-digit PIN number, then press ENTER. To change all PIN numbers to
the same number, enter the new setting within any zone, then press IN/OUT. All
zones will be changed at the same time. Press CLR/SIL to clear the display. Press
FUNC to advance to the next function.
4.3.25 FUNCTION 24 (SETTING THE STORE EVENTS OPTION)
Note:
This function is automatically downloaded from the SYSTEM 3505
PRISM LX when the SET button is pressed in the MULTIPLEX ADD/CHANGE/DEL
mode or when SYSTEM 3505 PRISM LX restarted.
When this function is enabled, the DGM panel will store date and time of all events
that occur when the data link is down. This information is then reported to the
SYSTEM 3505 PRISM LX when the data link is re-established.
To view or change Function 24, pr
ess “24”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display will read “24 -
Store Events.” A message will scroll on the first line:
The Store Events option is Disabled. To change the Store Events
option, press the TGGL button on the keypad. If the Store Events
option is enabled, the DGM panel will record the date and time that
events take place when the data link is down so they can be
reported to the SYSTEM 3505 PRISM LX at a later time. MUST BE
OFF unless you have a CAD system with proper software options.
Press CLR/SIL to clear display or FUNC to view next Function.
Press TGGL to enable/disable Store Events. Press CLR/SIL to clear the display.
Press FUNC to advance to the next function.
4.3.26 FUNCTION 25 (BACKPORCH)
This function sets the amount of delay time the transmitter remains on after the data
is sent from the DGM. The Backporch timing is set to five milliseconds for RS-422
and 10 milliseconds for radio. Changing this value may cause polling to stop from
this panel.
To view or change Function 25, press “25”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display wil
l read “25 -
Backporch = 5.” A message will scroll on the first line:
The Backporch timing is 005 milliseconds long. Set by SYSTEM
3505 PRISM LX, do not change. Press CLR/SIL to clear display or
FUNC to view next function.
Press CLR/SIL to clear the display. Press FUNC to advance to the next function.
4.3.27 FUNCTION 26 (AC DELAY)
This function sets the amount of time the DGM waits after it loses AC power before it
sends the ACPOWER FAIL signal to the System 3505 Prism Lx. The default of this
Summary of Contents for DGM-32/64