DGM INSTALLATION AND MAINTENANCE MANUAL
18
700135-0000 Rev. O
DGM-32/64-RF
4.7k Ohm
EOL
Trouble
Alarm
NC
NO
Typical Zone Connection
for Normally Open activation
with 4.7k ohm EOL resistor supervision.
Display / Keyboard
PCB PN 400373-0001
Zone 1/33
Zone 2/34
Zone 3/35
Zone 4/36
Zone 5/37
Zone 6/38
Zone 7/39
Zone 8/40
Zone 9/41
Zone 10/42
Zone 11/43
Zone 12/44
Zone 13/45
Zone 14/46
Zone 15/47
Zone 16/48
Zone 17/49
Zone 18/50
Zone 19/51
Zone 20/52
Zone 21/53
Zone 22/54
Zone 23/55
Zone 24/56
Zone 25/57
Zone 26/58
Zone 27/59
Zone 28/60
Zone 29/61
Zone 30/62
Zone 31/63
Zone 32/64
NO C NC
ALARM
TROUBLE
AC POWER
DC POWER
COMM
(XMIT)
RESET
1
2
3
READ
4
5
6
IN/
OUT
7
8
9
CLR/
SIL
TGGL
0
FUNC
ENTER
RESET
Beeper
- Press Clr/Sil button to
silence Beeper.
DC Power Led
– On when panel is
powered.
Comm (Xmit)
– Blinks when the
panel is communicating with
Prism Lx.
Reset Led
– Watchdog, blinks
occasionally to indicate panel is
functioning normal.
Reset Button
– Resets the panel
microcontroller.
Panel Door Tamper Switch
Alarm Led
– On when any zone
in panel is in Alarm.
Trouble Led
– On when any
Trouble condition present in
panel.
AC Power Led
– On when AC
power is present.
Read
– Enter zone #, then Read to
display zone status.
In/Out
– Enter Zone #, then In/Out
to place zone In or Out of Service
Clr/Sil
– Turns off beeper. Also
displays DGM Panel # and RTS
setting.
Enter
– used to Enter passnumber
and program panel
Func
– Enter Function #, then
Func to program panel.
TGGL
– Toggles a Function
setting when programming panel.
LCD Display
2 Line x 16 Character
Microcontroller Bd.
PN 400464-0002
P5
– Not Used
P0
– Ribbon Cable to J1 on 32
Zone Board(s), PN 400601- #
Reset Button
– Resets the panel
microcontroller.
P3
– Ribbon cable to Display
Panel, PN 400373-0001
U1
– Program Chip
32 Zone
Input Board
PN 400601- #
Power Led
– On when panel is
powered.
Watchdog Led
– blinks
occasionally to indicate panel is
functioning normal.
Comm Link
– Blinks when the
panel is communicating with
Prism Lx.
RXD
TXD
DET
XMIT
LOCKOUT
PTT
DGM
S1
JP1
SYS
P1
JP1
– Connects to P1 on
Microcontroller Bd., PN
400464-0002
P1
– To DB
Connector on Radio
Transceiver
RF Driver II Board
PN 400605-0001
SW2
SW1
33
-64
1
-32
33
-64
1
-32
Slide both SW1 and SW2 so they both point
to correct zone groups for the board.
Slide both
SW1
and
SW2
so they both point
to correct zone group for the board.
XMIT LOCKOUT Led
– When On indicates the transceiver
has been shutdown because it remained in Transmit mode
longer than 10 seconds. Power down panel to reset.
PTT
Led
– On when panel signals transceiver to transmit.
S1
– Jumper in DGM
position for panel use.
RXD
Led
– On when panel receiving data.
TXD
Led
– On when panel transmitting data.
DET
Led
– On when transceiver detects a
radio carrier.
Mounted on door.
Mounted on door.
Mounted on back panel.
Mounted on door.
BS1
– Trouble Relay Contacts -
Form C contacts, Rated 1 Amp @
24 Vdc
P4
– Cable to P4 on Power Supply
Board, PN 400467-0001
P0
P4
BS1
U1
P1
P3
J1
Manual
Fuse F1
, 4 Amp
Fuse F2
, 5 Amp
P4
– Cable to P4 on Microcontroller
Board, PN 400464-0002
Power Supply Board
PN 400467-0001
Mounted on back panel.
400601-0001:
32 Zone, 3k EOL
400601-0002:
32 Zone, 4.7k EOL
400601-0003:
8 Zone, 4.7k EOL
400601-0004:
16 Zone, 4.7k EOL
400601-0003:
24 Zone, 4.7k EOL
J1
– Ribbon Cable to P0
on Microcontroller Bd,
PN 400464-0002
When installing zone cable pair,
move 4.7k EOL resistor and place
across contact of Alarm initiating
device. Maximum length for zone
input is 1000 feet.
12 volt
12 AH
+
-
+
-
Digitize Inc.
158 Edison Rd, Lake Hopatcong NJ 07849
973-663-1011 www.Digitize-Inc.com
12V Battery,
Supervised
Mounted on back panel.
16 VAC
XFormer
Panel Input Voltage
115 VAC 50/60 Hz
@ 150 mA Max.
+13.5 VDC @ 100 mA. Max.
+5 VDC @ 100 mA Max.
Common
Connect
to Earth
(Safety)
Ground
Radio Transceiver
PN 900708 - #
Mounted on door.
BNC
Connector to
Antenna
DB Connector to
RF Driver II Bd.,
PN 400605-0001
On older style transceivers, the Power (upper) led is Red. The Status Led (lower)
lights Green when receiving data, Red when transmitting data. These Leds are not
installed on the newer models.
On newer transceivers, the Status Led lights Green when receiving data, Red
when transmitting data. This Led are not installed on the older models.
Note
– RF Driver Bd
PN 400589-0001
installed when using
older style
transceivers.
P4
BS1
Fuse F1
, ½ Amp
P1
– To JP1 on RF Driver II Bd.,
PN 400605-0001
TRA NZORB
TRA NZORB
G
A
S
T
U
B
E
Z
O
N
E
I
N
P
U
T
TO DECODE CK T
TO DECODE CK T
Lightning Protection
Circuit Typical for
Each Zone Input
Summary of Contents for DGM-32/64
Page 4: ......
Page 6: ......
Page 10: ......
Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...
Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...