DGM INSTALLATION AND MAINTENANCE MANUAL 

30 

 

700135-0000 Rev. O 

To view or change Function 14, press “14”, FUNC or, if you are viewing the previous 
function, just press FUNC. The second line of the display will read “14 - Set Format.” 
A message will scroll on the first line: 

The Multiplex Format is Enabled. Press the TGGL button to change. 
The Expanded Format should be enabled for use with SYSTEM 3505 
PRISM  LX  and  disabled  for  use  with  DPM  2000.  Press  CLR/SIL  to 
clear display or FUNC to view next Function. 

Press  TGGL  to  select/deselect  the  Expanded  Multiplex  Format.  Press  CLR/SIL  to 
clear the display. Press FUNC to advance to the next function. 

4.3.16 FUNCTION 15 (SETTING GLOBAL COMMAND RESPONSE) 

The  SYSTEM  3505  PRISM  LX  is  capable  of  sending  out  commands  to  a  group  of 
DGM  panels  at  the  same  time,  by  sen

ding  commands  to  DGM  0.  These  “grouped 

commands” could be used to synchronize the time of all the DGM panels, reset all of 
the DGM panels, or send a telegraph output from all of the panels at the same time. 
If  this  option  is  enabled,  the  specific  panel  will  respond  to  commands  directed  to 
DGM 0 as well as commands directed to its specific panel number. 

T

o  view  or  change  Function  15,  press  “15”,  then  FUNC  or,  if  you  are  viewing  the 

previous  function,  just  press  FUNC.  The  second  line  of  the  display  will  read 

“15  - 

DGM 0”. A message will scroll on the first line: 

Global  Command  response  is  Enabled.  Press  the  TGGL  button  to 
change.  Default  is  ON.  Press  CLR/SIL  to  clear  display  or  FUNC  to 
view next Function. 

Press  TGGL  to  select/deselect  the  Group  Commands  Option.  Press  CLR/SIL  to 
clear the display. Press FUNC to advance to the next function. 

4.3.17 FUNCTION 16 (SETTING DAY MODE/BURGLARY PANEL 

OPERATION)  

Sometimes, both security and fire signals are incorporated through the DGM panel. 
But during the daytime, when the building is occupied, the zones that will report fire 
signals 

should  remain  active,  while  the  zones  that  report  building  security  should  be 
bypassed.  These  bypassed  zones  would  not  report  alarm  conditions  but  would 
report a trouble condition. 

To select Day Mode operation, enable Function 16. A DGM operating in Day Mode 
will function in the following manner: 

Zone 1 of the panel now becomes the Day/Night switch. When the zone is shorted, 
the panel is in Day Mode; when the zone is open, the panel is in Night Mode. This 
zone could be tied to a key switch or keypad with relay outputs. 

Zone 2 now becomes the Burglary Panel for the entrance way where the keypad is 
located. Use Function 12 to assign a delay to zone 2 to allow enough time for zone 1 
to be shorted, placing the panel in Day Mode. If the panel is not placed in Day Mode 
before the delay on zone 2 runs out, an alarm will be reported on zone 2. 

The remaining zones in the panel operate as they normally would. Use Function 13 
to select the zones (security) to be bypassed during Day Mode operation. 

Summary of Contents for DGM-32/64

Page 1: ...64 M RLY RF INSTALLATION AND MAINTENANCE MANUAL Digitize Inc 158 Edison Road Lake Hopatcong New Jersey 07849 Tel 973 663 1011 Part Number 700135 0000 Fax 973 663 4333 Revision O E mail info digitize...

Page 2: ...Digitize Inc 158 Edison Road Lake Hopatcong NJ 07849 2217 The Digitize logo stylized is a registered trademark of Digitize Inc...

Page 3: ...ht to make changes to the specifications and material contained herein without prior notice The information and or examples including but not limited to circuitry wiring diagrams programming the opera...

Page 4: ......

Page 5: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installe...

Page 6: ......

Page 7: ...1 HANDLING 9 2 1 1 PRECAUTIONS 9 2 2 UNPACKING AND INSPECTION 9 2 3 CABINET MOUNTING 9 2 3 1 SITE PREPARATION 9 2 3 2 DISASSEMBLY PROCEDURE 9 2 3 3 MOUNTING INSTRUCTIONS 10 2 4 WIRING 10 2 4 1 CONDUI...

Page 8: ...PROGRAMMABLE FUNCTIONS 22 4 3 1 FUNCTION 0 SETTING DGM PANEL NUMBER 23 4 3 2 FUNCTION 1 SETTING FIRST ZONE NUMBER 23 4 3 3 FUNCTION 2 SETTING THE TIME 24 4 3 4 FUNCTION 3 SETTING PASSNUMBER 24 4 3 5 F...

Page 9: ...FUNCTION 34 SHOW BYPASS 37 4 3 36 FUNCTION 35 DISPLAY KEYPAD STATUS 37 4 3 37 FUNCTION 36 DISABLE TROUBLE LED 38 4 3 38 FUNCTION 37 FORCED PARITY 38 5 THEORY OF OPERATION 39 5 1 GENERAL 39 5 2 PANEL C...

Page 10: ......

Page 11: ...toring system and is suitable for monitoring fire and security alarms per NFPA 72 The system can also be used for energy management and process controls 1 2 DGM DESCRIPTION DIGITIZE models DGM 32 DGM...

Page 12: ...nput voltage to 16 VAC required for proper operation of the DGM 32 M RLY The sealed lead acid battery supplied provides the required 12 6 VDC for battery backup The battery is a 12 Amp Hour battery an...

Page 13: ...icates a BROWN enclosure 1 3 5 EXTERNAL KEYPAD In addition to the standard internal keypad you may order up to 16 optional external keypads to provide Entry Zone monitoring at each DGM Programming cap...

Page 14: ...Welded 0 063 steel hinged door with a cam lock and a baked enamel finish The removable inner door holds various interfaces the control panel and micro controller board The inner door is hinged to all...

Page 15: ...60 Degrees Celsius Storage Temperature Range 40 to 60 Degrees Celsius Operating Humidity Range 0 to 90 non condensing Storage Humidity Range 0 to 90 non condensing 1 5 F C C REQUIREMENTS The DGM comp...

Page 16: ...DGM INSTALLATION AND MAINTENANCE MANUAL 6 700135 0000 Rev O Figure 1 1 DGM 32 64 and DGM 32 64 RF...

Page 17: ...DGM INSTALLATION AND MAINTENANCE MANUAL 700135 0000 Rev O 7 Figure 1 2 DGM 32 64 RLY and DGM 32 64 RLY RF Figure 1 3 DGM 32 M RLY DGM 32 M RLY RF...

Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...

Page 19: ...to mount 2 3 CABINET MOUNTING 2 3 1 SITE PREPARATION The installation area should be well lit clean easily accessible and free from extremes of temperature and humidity Please refer to Section 1 4 7 T...

Page 20: ...shelf of the cabinet is used primarily for standby battery placement If the bottom shelf must be used for conduit entry make sure the wiring does not interfere with battery installation 2 4 2 FIELD W...

Page 21: ...nect the 32 Character LCD display and keyboard assembly This connector is keyed so the plug may only be inserted one way 2 5 2 5 CONNECTOR P4 This connector is used to connect the Main Board to the Po...

Page 22: ...nnel of a system wired for Style 6 operation 2 7 2 2 P1 This connector must be plugged into P1 of the main board of the DGM 2 7 3 RATINGS Maximum Circuit Voltage 5 volts Maximum Circuit Current 50 mA...

Page 23: ...ssembly is used to interface the two wire Multiplex communications line to the DGM The Audio Modem lines are supervised The SYSTEM 3505 PRISM LX location must have the Audio Modem line driver for prop...

Page 24: ...protection must be added for proper operation 2 10 2 1 Terminals 1 and 2 Channel A These terminals are not used with RF interface 2 10 2 2 P1 This connector must be plugged into P1 of the main board...

Page 25: ...rd is optional and is only used when the DGM is connected within 20 feet of the initiating device Use of these boards and configuration of the DGM is a special order These boards are available primari...

Page 26: ...ribbon cable plug from P0 of the main board or from P1 of the previous 32 Zone EOL board to P1 of the 32 Zone EOL board being installed 2 13 3 WIRING 2 13 3 1 BS1 BS8 Barrier strips BS1 BS8 contain te...

Page 27: ...6 keypads may be used for each DGM The keypads are primarily for Entry Zone security 2 15 1 WIRING 2 15 1 1 Eight Position Quick Disconnect This connector must be connected to RJ11 of the main board I...

Page 28: ...N 400605 0001 SW2 SW1 33 64 1 32 33 64 1 32 Slide both SW1 and SW2 so they both point to correct zone groups for the board Slide both SW1 and SW2 so they both point to correct zone group for the board...

Page 29: ...232 Fiber Optic and Polling Radio The multiplex data line is connected to the appropriate data input terminals on the data interface board The polarity of the multiplex data line must be observed for...

Page 30: ...he AC circuit breaker or local power disconnect switch in the OFF position connect the AC power wires to the transformer input terminal strip Then apply AC power to the DGM 3 5 2 DC POWER Connect the...

Page 31: ...X must have program revision 5 4 0 or higher for this capability The TRANSMITTER LED should now be flashing to indicate that the SYSTEM 3505 PRISM LX has recognized the new DGM and that the DGM is res...

Page 32: ...FUNCTION 36 FUNCTION 37 Setting DGM Panel Number Setting First Zone Number Setting the Time Setting the Passnumber Setting Beep on Alarm Setting Data Synchronization Setting Tamper Tilt Sensitivity C...

Page 33: ...ange the DGM Panel Number press 0 FUNC or just FUNC if this is the first function you are accessing The second line of the display will read 0 DGM NUM 0001 A message will scroll on the first line The...

Page 34: ...been restored from a data link down condition Presently the DGM does not need a time reference for any operational feature and it will operate properly even if the time is incorrect To view or change...

Page 35: ...r the display Press FUNC to advance to the next function 4 3 6 FUNCTION 5 SETTING DATA SYNCHRONIZATION Note This function is automatically downloaded from the SYSTEM 3505 PRISM LX when the SET button...

Page 36: ...el is operating from AC the clock reference should be AC power line During a power failure the clock reference should be internal crystal To view Function 7 press 7 FUNC or if you are viewing the prev...

Page 37: ...sage will display to indicate that the value was not valid and the original Ratio will display As indicated in the scrolling message one represents 10 On 90 Off two represents 20 On 80 Off etc The hig...

Page 38: ...second line of the display will read 11 Set RTS 040 A message will scroll on the first line The RTS timing is 040 milliseconds long Set by SYSTEM 3505 PRISM LX do not change Press CLR SIL to clear dis...

Page 39: ...ssage will scroll on the first line Not used Setting Zone to Bypass Press CLR SIL to clear display or FUNC to view next Function To select the desired zone enter the zone number then press READ or pre...

Page 40: ...oll on the first line Global Command response is Enabled Press the TGGL button to change Default is ON Press CLR SIL to clear display or FUNC to view next Function Press TGGL to select deselect the Gr...

Page 41: ...next Function Press TGGL to alternately select Open or Closed Index Press CLR SIL to clear the display Press FUNC to advance to the next function 4 3 19 FUNCTION 18 RESETTING PANEL TO FACTORY DEFAULTS...

Page 42: ...FUNC or if you are viewing the previous function just press FUNC The second line of the display will read 19 Trouble Relay A message will scroll on the first line The Trouble Relay is Disabled Press...

Page 43: ...or change Function 22 press 22 then FUNC or if you are viewing the previous function just press FUNC The second line of the display will read FUNC 22 ZN 01 NO The zone number and respective status ar...

Page 44: ...ss the TGGL button on the keypad If the Store Events option is enabled the DGM panel will record the date and time that events take place when the data link is down so they can be reported to the SYST...

Page 45: ...ion just press FUNC The second line of the display will read 27 Pin Length A message will scroll on the first line Pin Number length is 4 Press the TGGL button to change Press CLR SIL to clear display...

Page 46: ...nd the DGM displays DATA LINK DOWN on its LCD display The default for this function is 15 seconds The value can range between one to 255 seconds To view or change Function 30 press 30 then press FUNC...

Page 47: ...ion just press FUNC The second line of the display will read 33 RLY00 Off A message will scroll on the first line Toggle relays ON and OFF Enter relay number then press READ TGGL button will turn rela...

Page 48: ...uble LED control for bypassed zones is Disabled Press the TGGl button to change Activate trouble LED when zone is bypassed Press CLR SIL to clear display or FUNC to view next Function Press CLR SIL to...

Page 49: ...is open the tamper switch activates an audible alarm A corresponding Tamper message is displayed on the LCD and this change in status is reported to the SYSTEM 3505 PRISM LX Press CLR SIL to clear th...

Page 50: ...RISM LX You must have the IN OUT OF SERVICE option installed on your DGM panel Otherwise it will respond by displaying on the lower line of the display The operator at the SYSTEM 3505 PRISM LX also ha...

Page 51: ...the DGM When the door is closed the condition clears A mercury Tilt switch is located on the back of the display panel When the panel is tilted more than 45 degrees in any direction it will cause the...

Page 52: ...ROUBLE LED will be illuminated any time a zone is in trouble It will also be lit any time the DGM is in reset mode 5 3 2 3 AC POWER LED The AC POWER LED will be lit any time AC power is available to t...

Page 53: ...ndition is initiated by the closure of a normally open contact or the opening of a normally closed contact across any zone input pair This is indicated by the red ALARM LED Alarm zone information will...

Page 54: ...ccepted at the keypad 5 5 2 DISARMING OPERATION When a Security Entry Zone assigned to a keypad is violated the DGM begins an entry delay which has been programmed from one to 90 seconds At the same t...

Page 55: ...are secured enter a valid PIN number The GREEN LED will turn off the RED LED will turn on and the beeper will remain off The DGM will now send an ARMED condition to the head end The Entry Zone Delay...

Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...

Page 57: ...e to test ZONE ALARM Then proceed to the last device of each zone and open the circuit to test ZONE TROUBLE 6 2 ACCEPTANCE TESTING Use Table 6 1 to test all alarm and trouble initiating devices for ea...

Page 58: ...11 12 13 14 15 16 ALARM TROUBLE FUNCTION ZONE 17 18 19 20 21 22 23 24 ALARM TROUBLE FUNCTION ZONE 25 26 27 28 29 30 31 32 ALARM TROUBLE FUNCTION ZONE 33 34 35 36 37 38 39 40 ALARM TROUBLE FUNCTION ZO...

Page 59: ...e With respect to any products or art thereof not manufactured by Digitize only the warranty if any given by the manufacturer thereof applies EXCLUSIONS This limited warranty does not cover losses or...

Reviews: