DGM INSTALLATION AND MAINTENANCE MANUAL
700135-0000 Rev. O
33
Press TGGL to enable/disable the Alarm Relay. Press CLR/SIL to clear the display.
Press FUNC to advance to the next function.
Note:
This function must be disabled when any of the other Trouble Relay or
Telegraph Output options are selected.
4.3.22 FUNCTION 21 (SETTING THE CALL OUT OPTION)
The Call Out option is for polling radio panels only. When Function 21 is enabled,
the DGM panel will notify the SYSTEM 3505 PRISM LX of trouble or alarm without
waiting for the SYSTEM 3505 PRISM LX to poll.
To view or change Function 21, press “21”, then FUNC or, if you are viewing the
previous fun
ction, just press FUNC. The second line of the display will read “21 -
CALL OUT” A message will scroll on the first line:
The Call Out feature is Enabled. Press the TGGL button to change.
Normally OFF except in some RF applications. Press CLR/SIL to
clear display or FUNC to view next Function.
Press TGGL to enable/disable the Call Out Feature. Press CLR/SIL to clear the
display. Press FUNC to advance to the next function.
4.3.23 FUNCTION 22 (SETTING ZONE TO NORMALLY OPEN/CLOSED)
This function allows each zone in a DGM to be individually set for normally open or
normally closed.
To view or change Function 22, pre
ss “22”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the
display will read “FUNC
22 ZN 01
NO.” The zone number and respective status are represented. A message
will scroll on the first line:
Setting Zone to Normally Open/Closed. "NO" indicates the zone is
Normally Open. "NC" is Normally Closed. Use the READ button to
select the zone to view or update. Use the TGGL button to change
setting. The IN/OUT button will change all of the zones in the panel
at one time. Enter "0" for Normally Open, "1" for Normally Closed,
then press IN/OUT button. Press CLR/SIL to clear display or FUNC
to view next Function.
To select the desired zone enter the zone number, then press READ, or press
READ to advance sequentially through the zones. Press TGGL to change to
Normally Open or Normally closed. If you wish to change all zones to the same
setting, enter the new setting within any zone, then press IN/OUT. All zones will be
changed at the same time. Press CLR/SIL to clear the display. Press FUNC to
advance to the next function.
4.3.24 FUNCTION 23 (SETTING PIN NUMBERS)
This function is used to view or change PIN numbers, which protect access to
different levels of security.
To view or change Function 23, press “23”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display
will read “FUNC
23 PIN 1111.” A message will scroll on the first line: