DGM INSTALLATION AND MAINTENANCE MANUAL
32
700135-0000 Rev. O
Function 23 (Set Pin Number)
1111
Function 24 (Store Events Option)
Disabled
Function 25 (Backporch)
5 Milliseconds
Function 26 (AC Delay)
16 Seconds
Function 27 (Pin Length)
4
Function 28 (Activate KP)
All Off
Function 29 (Assign Add 2N)
No Zones to Follow
Function 30 (Link Down Delay)
16 Seconds
Function 31 (Stack Line Delay)
60 Seconds
Function 32 (Erase All Pin #'s)
Used to Erase All Stored Pin #'s
Function 33 (Toggle Relays)
RLY 0 Off
Function 34 (Display Bypass Zones)
Disabled
Function 35 (Display Keypad Status)
Disabled
Function 36 (Disable LED)
Disabled
Function 37 (Force Parity)
Enabled
4.3.20 FUNCTION 19 (SETTING TROUBLE RELAY)
When Function 19 is enabled, the DGM panel will toggle the Trouble Relay 0 (K1)
offwhenever any of the zones is in a Trouble condition. When none of the zones on the
DGM panel are in a Trouble condition, the Trouble Relay 0 (K1) will be on. If Function 19 &
20 areboth enabled at the same time, Function 19 will be ignored and the Trouble Relay 0
(K1) will turn off when any zone is in an Alarm condition.
To view or change Function 19, press
“19”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display
will read “19 - Trouble
Relay.” A message will scroll on the first line:
The Trouble Relay is Disabled. Press the TGGL button to change.
Default is OFF. Press CLR/SIL to clear display or FUNC to view next
Function.
Press TGGL to enable/disable the Trouble Relay. Press CLR/SIL to clear the display.
Press FUNC to advance to the next function.
Note:
This function must be disabled when any of the other Trouble Relay or
Telegraph Output options are selected.
4.3.21 FUNCTION 20 (SETTING ALARM RELAY)
When Function 20 is enabled, the DGM panel will turn the Trouble Relay (K1) off
whenever any of the zones are in a Alarm condition. When none of the zones on the
DGM panel are in a Alarm condition, the Trouble Relay 0 (K1) will be on. If Function
19 & 20 are both enabled at the same time, Function 19 will be ignored and the
Trouble Relay 0 (K1) will turn off when any zone is in a Alarm condition.
To view or change Function 20, press “20”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display will rea
d “20 -
Alarm Relay.” A message will scroll on the first line:
The Alarm Relay is Disabled. Press the TGGL button to change.
Default is OFF. Press CLR/SIL to clear display or FUNC to view next
Function.
Summary of Contents for DGM-32/64
Page 4: ......
Page 6: ......
Page 10: ......
Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...
Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...