DGM INSTALLATION AND MAINTENANCE MANUAL 

10 

 

700135-0000 Rev. O 

2.3.3  MOUNTING INSTRUCTIONS 

The  cabinet  supplied  with  the  standard  model  DGM  is  designed  for  surface 
mounting.  The  mounting  area  must  be  a  smooth,  clean  surface  on  a  permanent 
partition. The cabinet must  be securely fastened to the mounting surface using the 
four  mounting  holes.  For  this,  #10  or  1/4"  screws  are  suggested.  The  mounting 
location should be planned to allow full access to the top, bottom and sides for ease 
of  conduit  entry.  When  mounted,  panel  indicators  and  labels  should  be  plainly 
visible,  and  the  cabinet  door  must  be  able  to  swing  to  the  full  open  position. 
Following  these  guidelines  will  facilitate  ease  in  installation,  operation  and 
maintenance. 

Clean  out  any  dirt  produced  during  installation  and  reverse  the  procedure  for 
disassembly to reinstall electronics back into the enclosure. 

2.4  WIRING 

2.4.1  CONDUIT CONNECTIONS 

Connect  all  wiring  conduit  to  the  cabinet  in  accordance  with  applicable  National 
Electric Code, State and Local building code requirements. The cabinet is supplied 
with pre-stressed 1/2" knock-outs. Please note that the lower shelf of the cabinet is 
used  primarily  for  standby  battery  placement.  If  the  bottom  shelf  must  be  used  for 
conduit entry, make sure the wiring does not interfere with battery installation. 

2.4.2  FIELD WIRING 

Pull all power feeds and field wiring through the conduit and into the cabinet. Never 
place  power  feeds  and  field  wiring  in  the  same  conduit.  All  field  wiring  must  be 
tested for grounds, induced voltages, open and shorted circuits. All field wiring must 
be free of these conditions prior to connecting them  to peripheral devices or to the 
DGM. Do not connect field wiring until the DGM has been fully tested. Tag all wiring 
for  later  connection  to  the  unit.  Please  refer  to 

Section  3,  SYSTEM  INITIALIZATION. 

Failure to comply with these guidelines may cause damage to the unit. 

The  zone  inputs  are  designed  to  be  connected  to  field  wiring  with  a  maximum 
resistance of 750 Ohms. When a zone input is connected to field wiring longer than 
20 feet, lightning protection must be provided. The 32 zone EOL interface provides 
such protection. The panel must be properly grounded. Proper grounding is required 
both  for  safety  and  proper  operation  of  the  lightning  protection  and  ground  fault 
circuits. 

2.5  MAIN BOARD  

2.5.1  GENERAL 

This  is  the  main  microcontroller  board  for  the  panel.  It  contains  the  firmware  that 
operates the panel. 

Summary of Contents for DGM-32/64

Page 1: ...64 M RLY RF INSTALLATION AND MAINTENANCE MANUAL Digitize Inc 158 Edison Road Lake Hopatcong New Jersey 07849 Tel 973 663 1011 Part Number 700135 0000 Fax 973 663 4333 Revision O E mail info digitize...

Page 2: ...Digitize Inc 158 Edison Road Lake Hopatcong NJ 07849 2217 The Digitize logo stylized is a registered trademark of Digitize Inc...

Page 3: ...ht to make changes to the specifications and material contained herein without prior notice The information and or examples including but not limited to circuitry wiring diagrams programming the opera...

Page 4: ......

Page 5: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installe...

Page 6: ......

Page 7: ...1 HANDLING 9 2 1 1 PRECAUTIONS 9 2 2 UNPACKING AND INSPECTION 9 2 3 CABINET MOUNTING 9 2 3 1 SITE PREPARATION 9 2 3 2 DISASSEMBLY PROCEDURE 9 2 3 3 MOUNTING INSTRUCTIONS 10 2 4 WIRING 10 2 4 1 CONDUI...

Page 8: ...PROGRAMMABLE FUNCTIONS 22 4 3 1 FUNCTION 0 SETTING DGM PANEL NUMBER 23 4 3 2 FUNCTION 1 SETTING FIRST ZONE NUMBER 23 4 3 3 FUNCTION 2 SETTING THE TIME 24 4 3 4 FUNCTION 3 SETTING PASSNUMBER 24 4 3 5 F...

Page 9: ...FUNCTION 34 SHOW BYPASS 37 4 3 36 FUNCTION 35 DISPLAY KEYPAD STATUS 37 4 3 37 FUNCTION 36 DISABLE TROUBLE LED 38 4 3 38 FUNCTION 37 FORCED PARITY 38 5 THEORY OF OPERATION 39 5 1 GENERAL 39 5 2 PANEL C...

Page 10: ......

Page 11: ...toring system and is suitable for monitoring fire and security alarms per NFPA 72 The system can also be used for energy management and process controls 1 2 DGM DESCRIPTION DIGITIZE models DGM 32 DGM...

Page 12: ...nput voltage to 16 VAC required for proper operation of the DGM 32 M RLY The sealed lead acid battery supplied provides the required 12 6 VDC for battery backup The battery is a 12 Amp Hour battery an...

Page 13: ...icates a BROWN enclosure 1 3 5 EXTERNAL KEYPAD In addition to the standard internal keypad you may order up to 16 optional external keypads to provide Entry Zone monitoring at each DGM Programming cap...

Page 14: ...Welded 0 063 steel hinged door with a cam lock and a baked enamel finish The removable inner door holds various interfaces the control panel and micro controller board The inner door is hinged to all...

Page 15: ...60 Degrees Celsius Storage Temperature Range 40 to 60 Degrees Celsius Operating Humidity Range 0 to 90 non condensing Storage Humidity Range 0 to 90 non condensing 1 5 F C C REQUIREMENTS The DGM comp...

Page 16: ...DGM INSTALLATION AND MAINTENANCE MANUAL 6 700135 0000 Rev O Figure 1 1 DGM 32 64 and DGM 32 64 RF...

Page 17: ...DGM INSTALLATION AND MAINTENANCE MANUAL 700135 0000 Rev O 7 Figure 1 2 DGM 32 64 RLY and DGM 32 64 RLY RF Figure 1 3 DGM 32 M RLY DGM 32 M RLY RF...

Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...

Page 19: ...to mount 2 3 CABINET MOUNTING 2 3 1 SITE PREPARATION The installation area should be well lit clean easily accessible and free from extremes of temperature and humidity Please refer to Section 1 4 7 T...

Page 20: ...shelf of the cabinet is used primarily for standby battery placement If the bottom shelf must be used for conduit entry make sure the wiring does not interfere with battery installation 2 4 2 FIELD W...

Page 21: ...nect the 32 Character LCD display and keyboard assembly This connector is keyed so the plug may only be inserted one way 2 5 2 5 CONNECTOR P4 This connector is used to connect the Main Board to the Po...

Page 22: ...nnel of a system wired for Style 6 operation 2 7 2 2 P1 This connector must be plugged into P1 of the main board of the DGM 2 7 3 RATINGS Maximum Circuit Voltage 5 volts Maximum Circuit Current 50 mA...

Page 23: ...ssembly is used to interface the two wire Multiplex communications line to the DGM The Audio Modem lines are supervised The SYSTEM 3505 PRISM LX location must have the Audio Modem line driver for prop...

Page 24: ...protection must be added for proper operation 2 10 2 1 Terminals 1 and 2 Channel A These terminals are not used with RF interface 2 10 2 2 P1 This connector must be plugged into P1 of the main board...

Page 25: ...rd is optional and is only used when the DGM is connected within 20 feet of the initiating device Use of these boards and configuration of the DGM is a special order These boards are available primari...

Page 26: ...ribbon cable plug from P0 of the main board or from P1 of the previous 32 Zone EOL board to P1 of the 32 Zone EOL board being installed 2 13 3 WIRING 2 13 3 1 BS1 BS8 Barrier strips BS1 BS8 contain te...

Page 27: ...6 keypads may be used for each DGM The keypads are primarily for Entry Zone security 2 15 1 WIRING 2 15 1 1 Eight Position Quick Disconnect This connector must be connected to RJ11 of the main board I...

Page 28: ...N 400605 0001 SW2 SW1 33 64 1 32 33 64 1 32 Slide both SW1 and SW2 so they both point to correct zone groups for the board Slide both SW1 and SW2 so they both point to correct zone group for the board...

Page 29: ...232 Fiber Optic and Polling Radio The multiplex data line is connected to the appropriate data input terminals on the data interface board The polarity of the multiplex data line must be observed for...

Page 30: ...he AC circuit breaker or local power disconnect switch in the OFF position connect the AC power wires to the transformer input terminal strip Then apply AC power to the DGM 3 5 2 DC POWER Connect the...

Page 31: ...X must have program revision 5 4 0 or higher for this capability The TRANSMITTER LED should now be flashing to indicate that the SYSTEM 3505 PRISM LX has recognized the new DGM and that the DGM is res...

Page 32: ...FUNCTION 36 FUNCTION 37 Setting DGM Panel Number Setting First Zone Number Setting the Time Setting the Passnumber Setting Beep on Alarm Setting Data Synchronization Setting Tamper Tilt Sensitivity C...

Page 33: ...ange the DGM Panel Number press 0 FUNC or just FUNC if this is the first function you are accessing The second line of the display will read 0 DGM NUM 0001 A message will scroll on the first line The...

Page 34: ...been restored from a data link down condition Presently the DGM does not need a time reference for any operational feature and it will operate properly even if the time is incorrect To view or change...

Page 35: ...r the display Press FUNC to advance to the next function 4 3 6 FUNCTION 5 SETTING DATA SYNCHRONIZATION Note This function is automatically downloaded from the SYSTEM 3505 PRISM LX when the SET button...

Page 36: ...el is operating from AC the clock reference should be AC power line During a power failure the clock reference should be internal crystal To view Function 7 press 7 FUNC or if you are viewing the prev...

Page 37: ...sage will display to indicate that the value was not valid and the original Ratio will display As indicated in the scrolling message one represents 10 On 90 Off two represents 20 On 80 Off etc The hig...

Page 38: ...second line of the display will read 11 Set RTS 040 A message will scroll on the first line The RTS timing is 040 milliseconds long Set by SYSTEM 3505 PRISM LX do not change Press CLR SIL to clear dis...

Page 39: ...ssage will scroll on the first line Not used Setting Zone to Bypass Press CLR SIL to clear display or FUNC to view next Function To select the desired zone enter the zone number then press READ or pre...

Page 40: ...oll on the first line Global Command response is Enabled Press the TGGL button to change Default is ON Press CLR SIL to clear display or FUNC to view next Function Press TGGL to select deselect the Gr...

Page 41: ...next Function Press TGGL to alternately select Open or Closed Index Press CLR SIL to clear the display Press FUNC to advance to the next function 4 3 19 FUNCTION 18 RESETTING PANEL TO FACTORY DEFAULTS...

Page 42: ...FUNC or if you are viewing the previous function just press FUNC The second line of the display will read 19 Trouble Relay A message will scroll on the first line The Trouble Relay is Disabled Press...

Page 43: ...or change Function 22 press 22 then FUNC or if you are viewing the previous function just press FUNC The second line of the display will read FUNC 22 ZN 01 NO The zone number and respective status ar...

Page 44: ...ss the TGGL button on the keypad If the Store Events option is enabled the DGM panel will record the date and time that events take place when the data link is down so they can be reported to the SYST...

Page 45: ...ion just press FUNC The second line of the display will read 27 Pin Length A message will scroll on the first line Pin Number length is 4 Press the TGGL button to change Press CLR SIL to clear display...

Page 46: ...nd the DGM displays DATA LINK DOWN on its LCD display The default for this function is 15 seconds The value can range between one to 255 seconds To view or change Function 30 press 30 then press FUNC...

Page 47: ...ion just press FUNC The second line of the display will read 33 RLY00 Off A message will scroll on the first line Toggle relays ON and OFF Enter relay number then press READ TGGL button will turn rela...

Page 48: ...uble LED control for bypassed zones is Disabled Press the TGGl button to change Activate trouble LED when zone is bypassed Press CLR SIL to clear display or FUNC to view next Function Press CLR SIL to...

Page 49: ...is open the tamper switch activates an audible alarm A corresponding Tamper message is displayed on the LCD and this change in status is reported to the SYSTEM 3505 PRISM LX Press CLR SIL to clear th...

Page 50: ...RISM LX You must have the IN OUT OF SERVICE option installed on your DGM panel Otherwise it will respond by displaying on the lower line of the display The operator at the SYSTEM 3505 PRISM LX also ha...

Page 51: ...the DGM When the door is closed the condition clears A mercury Tilt switch is located on the back of the display panel When the panel is tilted more than 45 degrees in any direction it will cause the...

Page 52: ...ROUBLE LED will be illuminated any time a zone is in trouble It will also be lit any time the DGM is in reset mode 5 3 2 3 AC POWER LED The AC POWER LED will be lit any time AC power is available to t...

Page 53: ...ndition is initiated by the closure of a normally open contact or the opening of a normally closed contact across any zone input pair This is indicated by the red ALARM LED Alarm zone information will...

Page 54: ...ccepted at the keypad 5 5 2 DISARMING OPERATION When a Security Entry Zone assigned to a keypad is violated the DGM begins an entry delay which has been programmed from one to 90 seconds At the same t...

Page 55: ...are secured enter a valid PIN number The GREEN LED will turn off the RED LED will turn on and the beeper will remain off The DGM will now send an ARMED condition to the head end The Entry Zone Delay...

Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...

Page 57: ...e to test ZONE ALARM Then proceed to the last device of each zone and open the circuit to test ZONE TROUBLE 6 2 ACCEPTANCE TESTING Use Table 6 1 to test all alarm and trouble initiating devices for ea...

Page 58: ...11 12 13 14 15 16 ALARM TROUBLE FUNCTION ZONE 17 18 19 20 21 22 23 24 ALARM TROUBLE FUNCTION ZONE 25 26 27 28 29 30 31 32 ALARM TROUBLE FUNCTION ZONE 33 34 35 36 37 38 39 40 ALARM TROUBLE FUNCTION ZO...

Page 59: ...e With respect to any products or art thereof not manufactured by Digitize only the warranty if any given by the manufacturer thereof applies EXCLUSIONS This limited warranty does not cover losses or...