background image

 

 

8

 

 

 

 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

Install the evaporator coil on the supply side of the 
furnace ducting ONLY. 

 

An evaporator coil installed on the return air side of the 
ducting can cause condensation to form inside the heat 
exchanger, resulting in heat exchanger failure. This in 
turn, can result in death, bodily injury and/or property 
damage. 

 

A clearance of 15 cm (6") is required between the bottom of 
the coil drain pan and the top of the heat exchanger. If a heat 
pump is installed, a “dual-energy” thermostat, or other control 
is recommended, in order to prevent the simultaneous 
operation of the furnace and the heat pump. It also prevents a 
direct transition from heating by way of the heat pump to 
heating with oil. Refer to the thermostat instructions or those of 
another control used for the proper wiring. 

 

If a coil blower compartment is used, install air tight, motorized 
and automatic air dampers. Cold air coming from the coil and 
passing across the furnace can cause condensation and 
shorten the life of the heat exchanger. 
 

3 OPERATION 

3.1 START-UP 

Before starting up the unit, be sure to check that the following 
items are in compliance: 

 

1. 

The electrical installation, the oil supply system, the 
venting system, combustion air supply and ventilation; 

2. 

The blower access door is in place and the blower rail 
locking screws are well tightened; 

3. 

The Blocked Vent Shut-Off (BVSO) is installed according 
to instructions (for chimney venting); 

4. 

The oil supply valve is open; 

5. 

The burner ‘’Reset’’ button is well pushed in or re-armed; 

6. 

The preliminary air adjustments on the burner comply with 
the technical specifications in this manual; 

7. 

The blower speed adjustments for heating and air 
conditioning are appropriate and according to the 
specifications in this manual; 

8. 

The blower start/stop delays are satisfactory; 

9. 

The thermostat of the room is in the heating mode and is 
set higher than the ambient temperature. 

 

To start the unit, turn the main electrical switch on.  

3.2 

SEQUENCE OF OPERATION 
BECKETT AFG / RIELLO 40-F 

1.  Normally open contact (T-T) on primary relay 

closed when thermostat calls for heat; 

2. Beckett 

burner: The motor starts and spark is 

established. The pump pressure builds and the 
oil supply mechanism opens, admitting fuel to the 
nozzle; 

Riello burner: Burner motor starts. The burner 
motor fan pre-purges the combustion chamber 
and vent for 10 seconds, establishing the 
combustion air pattern. During this time the 
solenoid valve holding coil pressure is 
approximately 100 psig. The solenoid valve 
opens, allowing oil to flow  through the nozzle. At 
the same time, the burner motor ignition coil 
produces a spark; 

3.  Spark ignites oil droplets; 

4.  Cad cell senses flame and burner continues to 

fire. Ignition transformer ceases sparking (Riello 
R40-F); 

5.  After fan-limit control heats up to the factory set 

point, the circulating air blower and electronic air 
cleaner starts; 

6.  The circulating air blower and burner motor 

remain on until the thermostat is satisfied (AFG). 
The ignition transformer continues to spark 
(AFG). The solenoid valve remains open (R40-F); 

Thermostat is satisfied : 

7.  Primary relay contacts open, solenoid valve 

closes (R40-F), burner fan motor shuts down. The 
ignition transformer ceases sparking (AFG); 

8.  The fan-limit control bi-metal cools down to the 

factory set point of 90

o

 F (32

o

 C). At that point the 

circulating air blower stops. 

3.3 

CHECKS AND ADJUSTMENTS 

 

3.3.1 

P

URGING THE OIL LINE

 

 

Open the bleed port screw and start the burner. Allow the 
oil to drain into a container for at least 10 seconds. The oil 
should flow absolutely free of white streaks or air bubbles 
to indicate that no air is being drawn into the suction side 
of the oil piping and pump. Slowly close and tighten the 
bleed screw. Once closed, the flame will light up. 

 

 

3.3.2 

P

RESSURE ADJUSTMENT

 

 

The oil pressure must be adjusted according to the 
Technical Specifications of this manual. An adjustment 
screw and a connection for a pressure gauge are located 
on the oil pump for that purpose. Also refer to the burner 
instruction manual. 

Summary of Contents for AMT400B34-SM1PMA

Page 1: ...ON SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper with the unit or it...

Page 2: ...LATION OF ACCESSORIES 7 2 10 1 Air Conditioner or Heat Pump 7 3 OPERATION 8 3 1 START UP 8 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 8 3 3 CHECKS AND ADJUSTMENTS 8 3 3 1 Purging the oil line 8...

Page 3: ...4 TABLE 5 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS CANADA 15 TABLE 6 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS USA 15 TABLE 7 PARTS LIST 22 FIGURE 1 10 FIGURE 2 10 FIGURE 3 12 FIGURE 4 12 FIGURE 5 FURN...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...that the connections are direct and kept to a minimum The heater should also be located close to the centre of the air distribution system 2 2 ELECTRICAL SYSTEM CAUTION The exterior of the unit must...

Page 6: ...e thermal switch will shut down the oil burner The device will then need to be re armed MANUALLY Refer to the detailed instructions and wiring diagrams supplied with the BVSO for the installation and...

Page 7: ...1 or No 2 Heating Oil ASTM D396 U S or in Canada use No 1 or No 2 Furnace Oil A manual shut off valve and an oil filter shall be installed in sequence from tank to burner Be sure that the oil line is...

Page 8: ...emperature To start the unit turn the main electrical switch on 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 1 Normally open contact T T on primary relay closed when thermostat calls for heat 2 B...

Page 9: ...oper draft through the furnace The barometric damper must be mounted with the hinge pins in a horizontal position and the face of the damper vertical for proper functioning see instructions included w...

Page 10: ...erature from the supply air temperature 5 If the temperature rise is lower or exceeds the temperature specified in Table 1 p 13 change to the next lower or higher blower speed tap until the temperatur...

Page 11: ...bling the unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 9 After the cleaning replace the heat exchanger baffles flue collar plate and oil b...

Page 12: ...e motor base ALWAYS remove the belt tension before replacing it NEVER use a screwdriver to remove or install a belt This can damage the pulleys and other components Belt tension verification Ideally b...

Page 13: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 14: ...Operating voltage range Minimum ampacity for wiring sizing Max fuse size Amps BLOWER DATA Blower size Motor Motor pulley adj at 0 25 W C static pressure turns 3 5 3 5 3 3 Motor pulley adj at 0 50 W C...

Page 15: ...lue pipe Vertically above flue pipe 0 25 mm 9 Front From burner 0 6 m 24 Refer to the applicable installation code if a clearance reduction is required ex CSA B139 in Canada Table 6 Minimum clearances...

Page 16: ...16 Figure 5 Furnace dimensions DNS 0848 Rev E...

Page 17: ...17 Figure 6 Ladder Diagram Heating and Cooling AMT400B34 SM1PMA OLR350H28B...

Page 18: ...18 Figure 7 Wiring Diagram heating and cooling AMT400B34 SM1PMA OLR350H28B DNS 1016 Rev B...

Page 19: ...19 Figure 8 Wiring Diagram Heating AMT400B34 SM1PMA OLR350H289B DNS 1021 Rev B...

Page 20: ...20 COMPONENTS AND REPLACEMENT PARTS...

Page 21: ...21 Figure 9 Parts List With 4 speed motor PSC B50043B...

Page 22: ...mbly 24 B02850 Divider assembly 25 B02877 02 Front side panel insulation 26 B02875 02 Left lateral baffle 27 B02854 02 Front side panel assembly 28 B02853 02 Rear side panel assembly 29 B02870 02 Left...

Page 23: ...EMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES UL...

Page 24: ...ou Thermopompe 8 3 OP RATION 9 3 1 MISE EN MARCHE 9 3 2 S QUENCE DE FONCTIONNEMENT 9 3 2 1 S quence de fonctionnement Beckett AFG et Riello 40 F 9 3 3 V RIFICATIONS ET AJUSTEMENTS 9 3 3 1 Purge de la...

Page 25: ...EN CHELLE CHAUFFAGE ET CLIMATISATION 18 FIGURE 7 DIAGRAMME LECTRIQUE CHAUFFAGE ET CLIMATISATION 19 FIGURE 8 DIAGRAMME LECTRIQUE CHAUFFAGE 20 FIGURE 9 LISTE DE PI CES AVEC MOTEUR 4 VITESSES PSC 22 TAB...

Page 26: ...e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les renseignements sur la page 14 de ce manuel pour...

Page 27: ...t pas tanche et n est donc pas con u pour l ext rieur L appareil doit tre install de fa on prot ger les composants lectriques de l eau Une installation l ext rieur peut entra ner des conditions lectri...

Page 28: ...ibres des gicleurs sont bas s sur une pression de la pompe de 100 psi Pour s lectionner le calibre du gicleur toujours calculer le d bit d sir la pression r elle et d duire le calibre quivalent 2 3 2...

Page 29: ...a fin du cycle de refroidissement Si le fonctionnement n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 6 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement...

Page 30: ...requi re une pompe deux stages et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives d installation de la pompe pour d terminer la dimension du conduit utiliser en fonction de...

Page 31: ...s normalement ouverts T T sur le relais primaire se ferment quand le thermostat fait une demande de chauffage 2 Beckett AFG Le moteur d marre et une tincelle est d clench e La pression augmente dans l...

Page 32: ...appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r...

Page 33: ...urer la temp rature de l air au plus large embranchement sortant du pl num d alimentation en air situ juste en dehors de la ligne de radiation provenant de l changeur de chaleur une distance de 0 3 m...

Page 34: ...ou le tuyau fum e tous les ans mais il est recommand de faire v rifier votre unit par un technicien qualifi avant chaque saison de chauffage afin de d terminer si le nettoyage ou le remplacement de ce...

Page 35: ...ilateur puisqu ils sont lubrifi s de fa on permanente 4 7 1 Alignement des poulies Aligner la poulie du moteur et la poulie du ventilateur en d pla ant le moteur sur les rails du ventilateur Utiliser...

Page 36: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 37: ...E LECTRIQUE Volts Hertz Phase Ventilateur Volts Hertz Phase Br leur Consommation Amps Amp Minimum p r grosseur du fil Fusibles max Amps DONN ES TECHNIQUES DU VENTILATEUR Dimension du ventilateur Moteu...

Page 38: ...25 m 9 ARRI RE Porte d acc s au ventilateur 0 6 m 24 0 9 m 36 Fournaise et pl num 0 15 m 6 DESSUS Horizontale la conduite premiers 1 8 m 6 0 15 m 6 DESSOUS Fournaise plancher combustible 0 Horizontal...

Page 39: ...____________________________________________________________________________________ 17 Figure 5 Dimension HMT4 DNS 0848 R v E...

Page 40: ...18 Figure 6 Diagramme en chelle chauffage et climatisation AMT400B34 SM1PMA OLR350H28B...

Page 41: ...____________________________________________________________________________________ 19 Figure 7 Diagramme lectrique chauffage et climatisation AMT400B34 SM1PMA OLR350H28 DNS 1016 Rev B...

Page 42: ...20 Figure 8 Diagramme lectrique chauffage AMT400B34 SM1PMA OLR350H28 DNS 1021 Rev B...

Page 43: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 44: ...22 B50043 Rev B Figure 9 Liste de pi ces avec moteur 4 vitesses PSC...

Page 45: ...872 CACHE FILS 22 B02871 RENFORT DE PLANCHER 23 B02846 ASS PLANCHER 24 B02850 ASS SEPARATEUR 25 B02877 02 ISOLATION PANNEAU COTE AVANT 26 B02875 02 DEFLECTEUR LATERAL GAUCHE 27 B02854 02 ASS PANNEAU C...

Reviews: