background image

 

 

6

 

 

 

2.4 VENTING 

WARNING

 

 

Poisonous carbon monoxide gas hazard. 

 

Never install a hand operated damper in the vent pipe. 
However, any Underwriters Laboratories listed, 
electrically operated automatic type vent damper may be 
installed if desired. Be sure to follow the instructions 
provided with vent damper. Also, read and follow all 
instructions in this section of the manual. 

 

Failure to properly vent this furnace or other appliances 
can result in death, bodily injury and/or property damage. 

 
 

To ensure the safe and proper functioning of an oil furnace, it 
must always be connected to a flue with sufficient draft or to an 
approved side-wall venting system. In addition, it is strongly 
recommended to perform a complete inspection of all the 
existing venting systems. 

 

2.4.1 

M

ASONRY CHIMNEY

 

This furnace can be vented into an existing masonry chimney. 
However, the unit must not be vented into a chimney into 
which a solid fuel burning furnace is already being vented. 

 

Before venting this furnace into a chimney, its condition must 
be checked and repairs made, if necessary. Also, the chimney 
lining and dimensions must conform to local and national 
codes. 

 

2.4.2 

F

ACTORY 

B

UILT 

C

HIMNEYS

 

Oil fired furnaces are approved for use with “L” type vents. The 
unit may also be used with an approved chimney of proper 
dimensions and temperature ratings as specified in the 
installation code. Refer to chimney manufacturer’s instructions 
for proper installation. 

2.4.3 

D

RAFT 

R

EGULATOR

 

This unit may be installed with or without a draft 
regulator. However, it is recommended that a draft 
regulator be installed in cases where the draft is 
either high or variable due to external conditions. 
Follow the instructions provided with the regulator.

 

2.5 

BLOCKED VENT SHUT-OFF DEVICE 
(BVSO) FOR CHIMNEY VENTING 

CAUTION 

It is imperative that this device be installed by a qualified service 
technician. 

 

A positive pressure venting system (Sealed Combustion System 
or Direct Vent) 

MUST NOT

 use the BVSO. Follow the 

instructions supplied with the venting system. 

 

This device is designed to detect the insufficient evacuation of 
combustion gases in the event of a vent blockage. In such a 
case the thermal switch will shut down the oil burner. The 
device will then need to be re-armed MANUALLY.

 

R

efer to the detailed instructions and wiring diagrams 

supplied with the BVSO for the installation and wiring 
procedures. The length of wires supplied with the unit is 
such that the safety device must be installed between the 
flue outlet of the appliance and the draft regulator, as 
indicated in the instructions. 

 

It is also essential that the BVSO be maintained annually. 
For more details refer to the instructions supplied with the 
device itself, as well as Section 3 of this Manual. 
 

2.5.1 

BVSO

 

P

ERFORMANCE 

T

EST

 

 

The purpose of the following test is to check that the 
electrical outlet on the furnace, designated to the BVSO, 
is functional. 

 

1.  Start up the burner; 
2.  Remove the three-pole plug from the BVSO outlet on 

the furnace; 

3.  The burner must shut-off immediately, while the 

blower continues to run to the end of the cool-down 
cycle. 

 

If the test is not in line with the above, call a QUALIFIED 
SERVICE TECHNICIAN. 

 

2.6 

COMBUSTION AIR SUPPLY 
AND VENTILATION 

 

WARNING

 

 

Poisonous carbon monoxide gas hazard. 

 

Comply with NFPA 31 (U.S.) and CSA B139 (Canada) 
standards for the installation of Oil Burning 
Equipment and applicable provisions of local building 
codes to provide combustion and ventilation air. 

 

Failure to provide adequate combustion and 
ventilation air can result in death, bodily injury and/or 
property damage. 

 

Oil furnaces must have an adequate supply of combustion 
air. It is common practice to assume that older homes 
have sufficient infiltration to accommodate the combustion 
air requirement for the furnace. However, home 
improvements such as new windows, doors, and weather 
stripping have drastically reduced the volume of air 
infiltration into the home.

 

 

Refer to oil furnace installation codes relative to 
combustion and ventilation air requirements. Consult 
Section 2.1 in this manual, specifically for units installed in 
an enclosed space.  

 

Home air exhausters are common. Bathroom and kitchen 
fans, power vented clothes dryers and water heaters all 
tend to create a negative pressure condition in the home. 
Should this occur the chimney becomes less and less 
effective and can easily downdraft. In certain cases, 
mechanically supplied air, by way of a blower, interlocked 
with the unit, is necessary. It is the installer’s responsibility 
to check that. 

Summary of Contents for AMT400B34-SM1PMA

Page 1: ...ON SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper with the unit or it...

Page 2: ...LATION OF ACCESSORIES 7 2 10 1 Air Conditioner or Heat Pump 7 3 OPERATION 8 3 1 START UP 8 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 8 3 3 CHECKS AND ADJUSTMENTS 8 3 3 1 Purging the oil line 8...

Page 3: ...4 TABLE 5 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS CANADA 15 TABLE 6 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS USA 15 TABLE 7 PARTS LIST 22 FIGURE 1 10 FIGURE 2 10 FIGURE 3 12 FIGURE 4 12 FIGURE 5 FURN...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...that the connections are direct and kept to a minimum The heater should also be located close to the centre of the air distribution system 2 2 ELECTRICAL SYSTEM CAUTION The exterior of the unit must...

Page 6: ...e thermal switch will shut down the oil burner The device will then need to be re armed MANUALLY Refer to the detailed instructions and wiring diagrams supplied with the BVSO for the installation and...

Page 7: ...1 or No 2 Heating Oil ASTM D396 U S or in Canada use No 1 or No 2 Furnace Oil A manual shut off valve and an oil filter shall be installed in sequence from tank to burner Be sure that the oil line is...

Page 8: ...emperature To start the unit turn the main electrical switch on 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 1 Normally open contact T T on primary relay closed when thermostat calls for heat 2 B...

Page 9: ...oper draft through the furnace The barometric damper must be mounted with the hinge pins in a horizontal position and the face of the damper vertical for proper functioning see instructions included w...

Page 10: ...erature from the supply air temperature 5 If the temperature rise is lower or exceeds the temperature specified in Table 1 p 13 change to the next lower or higher blower speed tap until the temperatur...

Page 11: ...bling the unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 9 After the cleaning replace the heat exchanger baffles flue collar plate and oil b...

Page 12: ...e motor base ALWAYS remove the belt tension before replacing it NEVER use a screwdriver to remove or install a belt This can damage the pulleys and other components Belt tension verification Ideally b...

Page 13: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 14: ...Operating voltage range Minimum ampacity for wiring sizing Max fuse size Amps BLOWER DATA Blower size Motor Motor pulley adj at 0 25 W C static pressure turns 3 5 3 5 3 3 Motor pulley adj at 0 50 W C...

Page 15: ...lue pipe Vertically above flue pipe 0 25 mm 9 Front From burner 0 6 m 24 Refer to the applicable installation code if a clearance reduction is required ex CSA B139 in Canada Table 6 Minimum clearances...

Page 16: ...16 Figure 5 Furnace dimensions DNS 0848 Rev E...

Page 17: ...17 Figure 6 Ladder Diagram Heating and Cooling AMT400B34 SM1PMA OLR350H28B...

Page 18: ...18 Figure 7 Wiring Diagram heating and cooling AMT400B34 SM1PMA OLR350H28B DNS 1016 Rev B...

Page 19: ...19 Figure 8 Wiring Diagram Heating AMT400B34 SM1PMA OLR350H289B DNS 1021 Rev B...

Page 20: ...20 COMPONENTS AND REPLACEMENT PARTS...

Page 21: ...21 Figure 9 Parts List With 4 speed motor PSC B50043B...

Page 22: ...mbly 24 B02850 Divider assembly 25 B02877 02 Front side panel insulation 26 B02875 02 Left lateral baffle 27 B02854 02 Front side panel assembly 28 B02853 02 Rear side panel assembly 29 B02870 02 Left...

Page 23: ...EMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES UL...

Page 24: ...ou Thermopompe 8 3 OP RATION 9 3 1 MISE EN MARCHE 9 3 2 S QUENCE DE FONCTIONNEMENT 9 3 2 1 S quence de fonctionnement Beckett AFG et Riello 40 F 9 3 3 V RIFICATIONS ET AJUSTEMENTS 9 3 3 1 Purge de la...

Page 25: ...EN CHELLE CHAUFFAGE ET CLIMATISATION 18 FIGURE 7 DIAGRAMME LECTRIQUE CHAUFFAGE ET CLIMATISATION 19 FIGURE 8 DIAGRAMME LECTRIQUE CHAUFFAGE 20 FIGURE 9 LISTE DE PI CES AVEC MOTEUR 4 VITESSES PSC 22 TAB...

Page 26: ...e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les renseignements sur la page 14 de ce manuel pour...

Page 27: ...t pas tanche et n est donc pas con u pour l ext rieur L appareil doit tre install de fa on prot ger les composants lectriques de l eau Une installation l ext rieur peut entra ner des conditions lectri...

Page 28: ...ibres des gicleurs sont bas s sur une pression de la pompe de 100 psi Pour s lectionner le calibre du gicleur toujours calculer le d bit d sir la pression r elle et d duire le calibre quivalent 2 3 2...

Page 29: ...a fin du cycle de refroidissement Si le fonctionnement n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 6 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement...

Page 30: ...requi re une pompe deux stages et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives d installation de la pompe pour d terminer la dimension du conduit utiliser en fonction de...

Page 31: ...s normalement ouverts T T sur le relais primaire se ferment quand le thermostat fait une demande de chauffage 2 Beckett AFG Le moteur d marre et une tincelle est d clench e La pression augmente dans l...

Page 32: ...appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r...

Page 33: ...urer la temp rature de l air au plus large embranchement sortant du pl num d alimentation en air situ juste en dehors de la ligne de radiation provenant de l changeur de chaleur une distance de 0 3 m...

Page 34: ...ou le tuyau fum e tous les ans mais il est recommand de faire v rifier votre unit par un technicien qualifi avant chaque saison de chauffage afin de d terminer si le nettoyage ou le remplacement de ce...

Page 35: ...ilateur puisqu ils sont lubrifi s de fa on permanente 4 7 1 Alignement des poulies Aligner la poulie du moteur et la poulie du ventilateur en d pla ant le moteur sur les rails du ventilateur Utiliser...

Page 36: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 37: ...E LECTRIQUE Volts Hertz Phase Ventilateur Volts Hertz Phase Br leur Consommation Amps Amp Minimum p r grosseur du fil Fusibles max Amps DONN ES TECHNIQUES DU VENTILATEUR Dimension du ventilateur Moteu...

Page 38: ...25 m 9 ARRI RE Porte d acc s au ventilateur 0 6 m 24 0 9 m 36 Fournaise et pl num 0 15 m 6 DESSUS Horizontale la conduite premiers 1 8 m 6 0 15 m 6 DESSOUS Fournaise plancher combustible 0 Horizontal...

Page 39: ...____________________________________________________________________________________ 17 Figure 5 Dimension HMT4 DNS 0848 R v E...

Page 40: ...18 Figure 6 Diagramme en chelle chauffage et climatisation AMT400B34 SM1PMA OLR350H28B...

Page 41: ...____________________________________________________________________________________ 19 Figure 7 Diagramme lectrique chauffage et climatisation AMT400B34 SM1PMA OLR350H28 DNS 1016 Rev B...

Page 42: ...20 Figure 8 Diagramme lectrique chauffage AMT400B34 SM1PMA OLR350H28 DNS 1021 Rev B...

Page 43: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 44: ...22 B50043 Rev B Figure 9 Liste de pi ces avec moteur 4 vitesses PSC...

Page 45: ...872 CACHE FILS 22 B02871 RENFORT DE PLANCHER 23 B02846 ASS PLANCHER 24 B02850 ASS SEPARATEUR 25 B02877 02 ISOLATION PANNEAU COTE AVANT 26 B02875 02 DEFLECTEUR LATERAL GAUCHE 27 B02854 02 ASS PANNEAU C...

Reviews: