background image

 

 

5

 

2 INSTALLATION

 

The unit is shipped with a burner and its controls. It requires a 
115VAC power supply to the control panel and thermostat 
hook-up as shown on the wiring diagram, one or more oil line 
connections, suitable ductwork and connection to a properly 
sized vent.  

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that may 
apply are: 

CSA B139:

  

Installation code for oil burning equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

 Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

  Chimneys, Fireplaces, Vents and solid fuel 

burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1 or CSA C22.10

: Canadian Electrical Code. 

Only the latest issues of these codes may be used. 

2.1 

POSITIONING THE FURNACE 

WARNING 

 

Fire and explosion hazard. 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

 

Do not store or use gasoline or any other flammable 
substances near the furnace. 

 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

 

CAUTION 

This furnace is not watertight and is not designed for outdoor 
installation. It must be installed in such a manner as to protect 
its electrical components from water. Outdoor installation will 
lead to a hazardous electrical condition and to premature 
failure of the equipment. 

 

 

The minimum clearances from combustible material for 
each of the positions are specified in Table 4. 

 

If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit 
on a cement base 2.5 cm to 5.0 cm (1" to 2") thick. 

 

The unit must be installed in an area where the ambient and 
return air temperatures are above 15°C (60°F). In addition, the 
furnace should be installed as closely as possible to the vent, 
so that the connections are direct and kept to a minimum. The 
heater should also be located close to the centre of the air 
distribution system. 

2.2 ELECTRICAL 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted ground 
to minimize the risk of bodily harm, if ever an electrical 
problem develops. A green ground screw is supplied with 
the control box for that purpose.

  

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local codes. 

 

The control system depends on the correct polarity of the 
power supply. Connect “HOT” wire (H) and “NEUTRAL” 
wire (N) as shown in Figures 3 and 4, p. 17 and 18. 

 

A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main 
power panel and the unit. 

 

Only copper wire may be used for the 115V circuit on this 
unit. If wires need to be changed, the replacements must 
have the same temperature resistance as the originals. 
 

2.3 

INSTALLATION OF THE BURNER 

 

Also refer to the burner manufacturer’s instructions.  

 

1.  Position the mounting gasket between the mounting 

flange and the burner mounting plate. Align the holes 
in the burner mounting plate with the studs on the 
mounting flange and bolt securely in place. 

2.  Remove the burner drawer assembly or the air tube 

assembly; 

3.  Install the nozzle (refer to Technical Specifications, 

p.13); 

4.  Check the electrode settings; 

5.  Make the electrical connections; 

6.  Complete oil line connections. 

2.3.1 

N

OZZLES

 

The burner comes equipped with an appropriate nozzle. 
However, if another size or a replacement nozzle is 
required, use the manufacturer’s recommended spray 
angle and type a shown in Table 1 and based on a pump 
pressure of 100 psi.  

 

Always select nozzle sizes by working back from the 
desired flow rate at operating pressure and not the nozzle 
marking. 

2.3.2 

A

IR AND 

T

URBULATOR 

S

ETTINGS

 

Before starting the burner for the first time, adjust the air 
and turbulator settings to those listed in this manual. Once 
the burner becomes operational, final adjustments will be 
required. Refer to section 3 of this manual. 

Summary of Contents for AMT400B34-SM1PMA

Page 1: ...ON SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper with the unit or it...

Page 2: ...LATION OF ACCESSORIES 7 2 10 1 Air Conditioner or Heat Pump 7 3 OPERATION 8 3 1 START UP 8 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 8 3 3 CHECKS AND ADJUSTMENTS 8 3 3 1 Purging the oil line 8...

Page 3: ...4 TABLE 5 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS CANADA 15 TABLE 6 MINIMUM CLEARANCES COMBUSTIBLE MATERIALS USA 15 TABLE 7 PARTS LIST 22 FIGURE 1 10 FIGURE 2 10 FIGURE 3 12 FIGURE 4 12 FIGURE 5 FURN...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...that the connections are direct and kept to a minimum The heater should also be located close to the centre of the air distribution system 2 2 ELECTRICAL SYSTEM CAUTION The exterior of the unit must...

Page 6: ...e thermal switch will shut down the oil burner The device will then need to be re armed MANUALLY Refer to the detailed instructions and wiring diagrams supplied with the BVSO for the installation and...

Page 7: ...1 or No 2 Heating Oil ASTM D396 U S or in Canada use No 1 or No 2 Furnace Oil A manual shut off valve and an oil filter shall be installed in sequence from tank to burner Be sure that the oil line is...

Page 8: ...emperature To start the unit turn the main electrical switch on 3 2 SEQUENCE OF OPERATION BECKETT AFG RIELLO 40 F 1 Normally open contact T T on primary relay closed when thermostat calls for heat 2 B...

Page 9: ...oper draft through the furnace The barometric damper must be mounted with the hinge pins in a horizontal position and the face of the damper vertical for proper functioning see instructions included w...

Page 10: ...erature from the supply air temperature 5 If the temperature rise is lower or exceeds the temperature specified in Table 1 p 13 change to the next lower or higher blower speed tap until the temperatur...

Page 11: ...bling the unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 9 After the cleaning replace the heat exchanger baffles flue collar plate and oil b...

Page 12: ...e motor base ALWAYS remove the belt tension before replacing it NEVER use a screwdriver to remove or install a belt This can damage the pulleys and other components Belt tension verification Ideally b...

Page 13: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 14: ...Operating voltage range Minimum ampacity for wiring sizing Max fuse size Amps BLOWER DATA Blower size Motor Motor pulley adj at 0 25 W C static pressure turns 3 5 3 5 3 3 Motor pulley adj at 0 50 W C...

Page 15: ...lue pipe Vertically above flue pipe 0 25 mm 9 Front From burner 0 6 m 24 Refer to the applicable installation code if a clearance reduction is required ex CSA B139 in Canada Table 6 Minimum clearances...

Page 16: ...16 Figure 5 Furnace dimensions DNS 0848 Rev E...

Page 17: ...17 Figure 6 Ladder Diagram Heating and Cooling AMT400B34 SM1PMA OLR350H28B...

Page 18: ...18 Figure 7 Wiring Diagram heating and cooling AMT400B34 SM1PMA OLR350H28B DNS 1016 Rev B...

Page 19: ...19 Figure 8 Wiring Diagram Heating AMT400B34 SM1PMA OLR350H289B DNS 1021 Rev B...

Page 20: ...20 COMPONENTS AND REPLACEMENT PARTS...

Page 21: ...21 Figure 9 Parts List With 4 speed motor PSC B50043B...

Page 22: ...mbly 24 B02850 Divider assembly 25 B02877 02 Front side panel insulation 26 B02875 02 Left lateral baffle 27 B02854 02 Front side panel assembly 28 B02853 02 Rear side panel assembly 29 B02870 02 Left...

Page 23: ...EMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES UL...

Page 24: ...ou Thermopompe 8 3 OP RATION 9 3 1 MISE EN MARCHE 9 3 2 S QUENCE DE FONCTIONNEMENT 9 3 2 1 S quence de fonctionnement Beckett AFG et Riello 40 F 9 3 3 V RIFICATIONS ET AJUSTEMENTS 9 3 3 1 Purge de la...

Page 25: ...EN CHELLE CHAUFFAGE ET CLIMATISATION 18 FIGURE 7 DIAGRAMME LECTRIQUE CHAUFFAGE ET CLIMATISATION 19 FIGURE 8 DIAGRAMME LECTRIQUE CHAUFFAGE 20 FIGURE 9 LISTE DE PI CES AVEC MOTEUR 4 VITESSES PSC 22 TAB...

Page 26: ...e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les renseignements sur la page 14 de ce manuel pour...

Page 27: ...t pas tanche et n est donc pas con u pour l ext rieur L appareil doit tre install de fa on prot ger les composants lectriques de l eau Une installation l ext rieur peut entra ner des conditions lectri...

Page 28: ...ibres des gicleurs sont bas s sur une pression de la pompe de 100 psi Pour s lectionner le calibre du gicleur toujours calculer le d bit d sir la pression r elle et d duire le calibre quivalent 2 3 2...

Page 29: ...a fin du cycle de refroidissement Si le fonctionnement n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 6 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement...

Page 30: ...requi re une pompe deux stages et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives d installation de la pompe pour d terminer la dimension du conduit utiliser en fonction de...

Page 31: ...s normalement ouverts T T sur le relais primaire se ferment quand le thermostat fait une demande de chauffage 2 Beckett AFG Le moteur d marre et une tincelle est d clench e La pression augmente dans l...

Page 32: ...appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r...

Page 33: ...urer la temp rature de l air au plus large embranchement sortant du pl num d alimentation en air situ juste en dehors de la ligne de radiation provenant de l changeur de chaleur une distance de 0 3 m...

Page 34: ...ou le tuyau fum e tous les ans mais il est recommand de faire v rifier votre unit par un technicien qualifi avant chaque saison de chauffage afin de d terminer si le nettoyage ou le remplacement de ce...

Page 35: ...ilateur puisqu ils sont lubrifi s de fa on permanente 4 7 1 Alignement des poulies Aligner la poulie du moteur et la poulie du ventilateur en d pla ant le moteur sur les rails du ventilateur Utiliser...

Page 36: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 37: ...E LECTRIQUE Volts Hertz Phase Ventilateur Volts Hertz Phase Br leur Consommation Amps Amp Minimum p r grosseur du fil Fusibles max Amps DONN ES TECHNIQUES DU VENTILATEUR Dimension du ventilateur Moteu...

Page 38: ...25 m 9 ARRI RE Porte d acc s au ventilateur 0 6 m 24 0 9 m 36 Fournaise et pl num 0 15 m 6 DESSUS Horizontale la conduite premiers 1 8 m 6 0 15 m 6 DESSOUS Fournaise plancher combustible 0 Horizontal...

Page 39: ...____________________________________________________________________________________ 17 Figure 5 Dimension HMT4 DNS 0848 R v E...

Page 40: ...18 Figure 6 Diagramme en chelle chauffage et climatisation AMT400B34 SM1PMA OLR350H28B...

Page 41: ...____________________________________________________________________________________ 19 Figure 7 Diagramme lectrique chauffage et climatisation AMT400B34 SM1PMA OLR350H28 DNS 1016 Rev B...

Page 42: ...20 Figure 8 Diagramme lectrique chauffage AMT400B34 SM1PMA OLR350H28 DNS 1021 Rev B...

Page 43: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 44: ...22 B50043 Rev B Figure 9 Liste de pi ces avec moteur 4 vitesses PSC...

Page 45: ...872 CACHE FILS 22 B02871 RENFORT DE PLANCHER 23 B02846 ASS PLANCHER 24 B02850 ASS SEPARATEUR 25 B02877 02 ISOLATION PANNEAU COTE AVANT 26 B02875 02 DEFLECTEUR LATERAL GAUCHE 27 B02854 02 ASS PANNEAU C...

Reviews: