70
4.8. Supply Air Temperature Sensor
The Supply Air Temperature Sensor is a resistive NTC Bulb type device with a 10 foot cable.
The temperature range is -58.0° F to 212.0º F and the environmental rating is IP67. The failure
mode of this device will display a reading of -623.3º F if the sensor is open, and display a
reading of 687.3º F if the sensor is shorted. The Desert Aire replacement part number for the
Supply Air Temperature Sensor is available by calling our service department.
4.9. Intake Air Temperature and Relative Humidity Sensor
The Intake Air and Relative Humidity Sensor is internally mounted in the air stream of the unit,
behind the air filter. The Temperature Sensor is a resistive NTC Bulb type device. The failure
mode of this device will display a reading of -623.3º F if the sensor is open, and display a
reading of 687.3º F if the sensor is shorted. A reading of 0.0% humidity indicates a failure of
the RH sensor. The Desert Aire replacement part number for the Intake Air Temperature and
Relative Humidity Sensor is available by calling our service department.
4.10. Air Flow Switch
The Air Flow Switch is internally mounted in the air stream of your dehumidifier. The Desert
Aire replacement part number for the Air Flow Switch is available by calling our service
department.
Desert Aire - CM3500 Manual
Summary of Contents for CM3500 Series
Page 2: ...2 ...
Page 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Page 6: ...6 Desert Aire CM3500 Manual ...
Page 10: ...10 Desert Aire CM3500 Manual ...
Page 16: ...16 Desert Aire CM3500 Manual ...
Page 60: ...60 Desert Aire CM3500 Manual ...
Page 66: ...66 Desert Aire CM3500 Manual ...
Page 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Page 79: ...79 Desert Aire CM3500 Manual ...