68
When unlocked, the zone set point can be modified by using the
UP
and
DOWN
buttons. Simply press one of these buttons to display the set point. When the
appropriate set point is displayed, wait a few seconds and the set point will be saved.
The remote room sensor with address 2 can also be used to temporarily override
occupancy from one to nine hours. To override occupancy, press the
SLEEP
button on
the left side of the Remote Room Sensor. The
SLEEP
button, symbolized as a
crescent moon on the left side of the sensor, is the fourth button from the top. An icon
showing a crescent moon and the number of hours the occupancy will be overridden
is displayed. To increase the hours, press the
SLEEP
button repeatedly until the
appropriate number of hours is displayed. To disable the temporary override, press the
SLEEP
button until “0” (zero) hours is displayed. The temporary override will now end.
Additionally, any Remote Room Sensor connected to the CM3500 will also display
important information such as an alarm condition, the occupied mode and whether the
room sensor network connection has failed. An alarm condition is displayed as “ALr”
and will flash between the room temperature and “ALr.” A bell icon will also blink on
the display. The occupancy of the unit will be displayed as a house icon to the left of
the room temperature. If the house icon is empty, the dehumidifier is in the
un-occupied mode. If a human figure is in the house, the dehumidifier is in the
occupied mode. If the network connection has failed, “oLn” is displayed to indicate
that the Remote Room Sensor is offline.
Internal setup of the remote room sensor is accomplished by pressing the
DOWN
button and, while holding the
DOWN
button, pressing the
UP
button for 4 seconds.
When the display blinks “Par”, keep pressing the
UP
button, release the
DOWN
button
and press the bottom button on the left hand side of the sensor for three seconds.
The display will now show the current device address as “Ad01”. Select and modify
respectively with the bottom button on the left hand side of the sensor, the
UP
and
DOWN
buttons. “Ad01” is the pAD address, settable from 1 – 32. “br01” is the baud
rate and needs to be set at 0. “En01” set to 0 disables the buzzer. “Pc01” is the offset
of the zone temperature from -9.9 to 9.9.
Figure 73
Desert Aire - CM3500 Manual
Summary of Contents for CM3500 Series
Page 2: ...2 ...
Page 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Page 6: ...6 Desert Aire CM3500 Manual ...
Page 10: ...10 Desert Aire CM3500 Manual ...
Page 16: ...16 Desert Aire CM3500 Manual ...
Page 60: ...60 Desert Aire CM3500 Manual ...
Page 66: ...66 Desert Aire CM3500 Manual ...
Page 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Page 79: ...79 Desert Aire CM3500 Manual ...