62
3.1.3. Motor Fault (Figure 71)
This is a Manual Reset Alarm. The Motor Fault Alarm will only be activated when any
of the motor overload devices wired into digital input 3 indicate an overloaded
condition. In this state, the unit will stop and not restart until the alarm condition is
reset manually. The red ALARM LED on the display will stay lit until the alarm is reset.
Figure 71
3.1.4. High Discharge Pressure Circuit A or Circuit B
This is a Manual Reset Alarm. The High Discharge Pressure Alarm is activated when
the Discharge Pressure rises above the High Pressure Trip Set Point (see Section
2.6.4). The unit will stop and not restart until the alarm condition is reset manually.
The red ALARM LED on the display will stay lit until the alarm is reset.
3.1.5. Multiple Low Suction Pressure Alarms Circuit A or Circuit B
This is an Automatic Reset Alarm that becomes a Manual Reset Alarm after a number
of attempts. If the low suction pressure cycle occurs 3 (adjustable) times in a 1
(adjustable) hour time period, then an alarm will be indicated and recorded in the
alarm history as a multiple suction pressure alarm. This alarm will be reset, by the
controller after a 2 (adjustable) hour time delay. This controller reset will be tried 3
(adjustable) times in a 36 (adjustable) hour period. After the fourth controller reset, if
the multiple suction pressure alarm occurs again, an operator initiated reset will be
required to restart the unit.
3.1.6. Room Reset Network Failure
This is an Automatic Reset Alarm. The Room Reset Network Failure Alarm is activated
when the Remote Room Sensor is offline or disconnected from the controller. In this
state, the unit will be placed in SAT Control and will run in this mode with the alarm
active. When the Remote Room Sensor is back online with the controller, the unit will
return to Zone Reset Control automatically. The red ALARM LED on the display will
stay lit until the alarm is reset.
Desert Aire - CM3500 Manual
Summary of Contents for CM3500 Series
Page 2: ...2 ...
Page 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Page 6: ...6 Desert Aire CM3500 Manual ...
Page 10: ...10 Desert Aire CM3500 Manual ...
Page 16: ...16 Desert Aire CM3500 Manual ...
Page 60: ...60 Desert Aire CM3500 Manual ...
Page 66: ...66 Desert Aire CM3500 Manual ...
Page 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Page 79: ...79 Desert Aire CM3500 Manual ...