46
Figure 47
Pressing
the
DOWN
key will display the Supply Blower PID screen shown on
Figure 48. The Supply Blower PID screen allows the PID loop for the blower
speed to be modified. The PID setting of the Gain (or Proportional Band),
Reset (or Integral) and the Rate (or Derivative) can be modified here. The
range of the Gain is 0 to 32767. The range of the Reset is 0 to 32767. The
range of the Rate is 0 to 32767. The Set Point of the Fan DP is also set here.
The actual fan DP and Loop Output are displayed here to aid in the tuning of
the
PID
loop.
To modify these set points, press the
ENTER
key and use the arrow keys
until the desired setting is shown. Pressing the
ENTER
key will now change
the
set
point.
Figure 48
Pressing
the
DOWN
key will display the Manual Blower Setup screen shown
on Figure 49. The supply air blower can be set to manual control here. The
Man S/A Command will be used for the speed of the blower. The Man E/A
Command will be used for the speed of the exhaust blower. These commands
can be set from 0.0% to 100.0%.
Desert Aire - CM3500 Manual