51
Figure 55
2.6.2.1 Reheat Control Settings (Figure 56)
This screen allows the Reheat Control PID Gain (or Proportional Band), Reset
(or Integral) and the Rate (or Derivative) to be modified for loop tuning. The
range of the Gain is 0.0º F to 999.9º F. The range of the Reset is 0 to 999.
The range of the Rate is 0 to 999. The Supply Air Temperature, Set Point and
actual loop output are displayed here to aid in the tuning of the PID loop.
To modify these set points, press the
ENTER
key and use the arrow keys until
the desired setting is shown. Press the
ENTER
key to accept the set point
value.
To return to the Parameter Settings, press the
Esc
key.
Figure 56
2.6.2.2 Auxiliary Heat Control Settings (Figure 57)
This screen allows the Auxiliary Heat PID Gain (or Proportional Band), Reset
(or Integral) and the Rate (or Derivative) to be modified for loop tuning. The
range of the Gain is 0.0º F to 999.9º F. The range of the Reset is 0 to 999.
The range of the Rate is 0 to 999. The Supply Air Temperature, Set Point and
Desert Aire - CM3500 Manual