2.6.1.5 Blower Setup (Figures 46-49)
The Blower Setup screens allow configuration of the EC supply fans used on
Aura units. If an Aura unit is not provided, the manual blower setup screen will
be the only screen shown. The Fan type is selected here, as well as the
altitude of the site, which are required to calculate the correct CFM. The Fan
DP and the calculated CFM are shown at the bottom of this screen for
informational
purposes
only.
Figure 46
Pressing
the
DOWN
key will display the screen on Figure 47. This screen is
used to modify the minimum air flow set point. The minimum air flow set point
is used to set the low air flow alarm for Aura units. The fan DP has to be lower
than 80% of the set point to set the alarm. The fan DP is shown on this screen
for informational purposes only. The filtering time is used to filter any abrupt
changes in the reading of the air pressure transducer. This can be set from
1 to 99 seconds, with 1 having the least amount of filtering and 99 the most
amount of filtering.