32
Figure 26
2.4.3. Supply Air Temperature Setpoint (Figure 27)
This screen will only be shown if the zone or outside air reset options are not selected.
This screen allows the supply air temperature set point to be modified. The value of
the set point ranges from 45.0º F to 99.9º F with a 72.0º F default. To modify the
set point, press the
ENTER
key and use the
UP
and
DOWN
arrow keys until the
desired setting is shown. Press the
ENTER
key to accept the set point value.
To return to the TEMPERATURE SETTINGS MENU, press the
Esc
key.
Figure 27
2.4.4. Zone Reset Setpoints (Figure 28)
In the Zone Reset mode of operation, the Supply Air Temperature Setpoint is
calculated based upon the actual zone air temperature and the zone air temperature
set point and will fall between the High and Low Limit Set Points. This mode requires
the remote room sensor be installed in the conditioned space. See section 2.4.4.1 for
operation. As the zone air temperature increases above the zone air set point, the
set point is continuously modified to achieve a faster return to set point. The same logic
applies to a decrease in zone air temperature below the set point. The High and Low
Limit Set Points create the band within which the calculated zone air temperature
set point will fall.
Desert Aire - CM3500 Manual
Summary of Contents for CM3500 Series
Page 2: ...2 ...
Page 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Page 6: ...6 Desert Aire CM3500 Manual ...
Page 10: ...10 Desert Aire CM3500 Manual ...
Page 16: ...16 Desert Aire CM3500 Manual ...
Page 60: ...60 Desert Aire CM3500 Manual ...
Page 66: ...66 Desert Aire CM3500 Manual ...
Page 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Page 79: ...79 Desert Aire CM3500 Manual ...