80
Operating the PV inverter
Pm
fstart
fstop
Gradient (%/Hz)
f(Hz)
P
Pm
P
frecovery
fstart
fstop
f(Hz)
Gradient (%/Hz)
Figure 7.19.: LVD Curve power vs. frequency
Figure 7.20.: MVD Curve power vs. frequency
nOTE
The Power vs
Frequency function is
required for LVD and
MVD. Please make
sure the Mode is ON
and do not turn off.
Figure 7.21.: Power vs. Frequency
adjustable parameters
Parameter
adjustable Values Description
Actual / Rated Power
Actual or Rated can be selected
Start frequency
50.00 ... 55.00
The frequency when the power reduction starts
Stop frequency
Stop frequency means the frequency when
power = 0. This value is calculated by the gra-
dient and the start frequency.
Recovery frequency
50.00 ... 55.00
This feature is only for MVD. This value is
equal to the frequency of the grid connection.
Gradient
0 ... 100 %
This feature adjusts the gradient. The units are
% / Hz.
Recovery Time
Not applicable for LVD or MVD
Mode
ON | OFF
Switches the feature on and off