Wiring the Inverter
Figure 6.17.: Terminal resistor switch for Multi-inverter Connection
To engage the internal Terminal Resistor, place switch number 2 on the communication module in
the on position. See figure 6.17 for more information.
Baud Rate
Programmable, 2400/4800/9600/19200/38400, default = 19200
Data Bit
8
Stop Bit
1
Parity
N/A
Table 6.4.: RS485 Data Format
6.5.2 EPO (Emergency Power Off) Connections
The SOLIVIA 10 TL / 15 TL / 20 TL / 30 TL provides two sets of emergency power off functions.
When the outer external switch is shorted, the inverter will shut down immediately. Please see
Table 6.5 for the pin definition.
PIn
Definition
1
EPO1
2
EPO1
3
N/A
4
EPO2
5
EPO2
6
N/A
7
N/A
8
N/A
Table 6.5.:
EPO pin assignment