Operating the PV inverter
adjustable parameters
Parameter
adjustable values
Description
Qs limit
(Q/Sn)
0 ... 60%
Ind 44%
inductive | capacitive
Qi limit
(Q/Sn)
0 ... 60%
Cap 44%
inductive | capacitive
V1s
230 ... 264.5 V
248.4 V
V2s
230 ... 264.5 V
253 V
V1i
184 ... 230 V
211.6 V
V2i
184 ... 230 V
207 V
Plock-in*
10 ... 100%
20% is shown but use value from the grid
operator
Plock-out*
5 ... 10%
5% is shown but use value from the grid
operator
Delay time
0 ... 120 s
10 s
Mode
Curve A I Curve B I
OFF
This switches between Curve A and Curve B or
OFF
*This item is only adjustable and enabled if Country settings is Italy CEI 0-21 or Italy A70.
7.3.6.4.7 LVFrT Low Voltage Fault ride Through (LVFrT)
This feature is available for CEI 0-21 and A70.
This feature allows the Fault Ride Through features to be set.
Values before the FRT condition P
FRT
, Q
FRT
V/Vn
110%
90%
40%
0%
85%
0
200
400
ms
Normal operation
Inverter must not
disconnect
Inverter could
disconnect
V < 0.9 V
n
The inverter is allowed
to reduce the power in
respect to the max output
current
Figure 7.36.: Low Voltage Fault Ride Through graph