Operating the PV inverter
7.3.6.3.3 Constant cos φ
This feature is available for LVD and MVD grids. This feature allows the user to set up a constant
cos
φ.
Figure 7.22.: Constant cos φ settings page
adjustable parameters
Parameter
adjustable values
Description
cos φ
inductive | capacitive
Sets the cos φ to the adjusted value.
Ind 0.8 ... Ind 0.99, 1,
Cap 0.8 ... Cap. 0.99
Mode
ON | OFF
Switches the feature on and off
7.3.6.3.4
cos
φ(p)
This feature is available for LVD and MVD grids.
With this feature a cos φ can be assigned to a power ratio P/Pn.
The following curve is an example how the values could be set: