Description
Default
Export Configure List
Export all the mapping and save as a file in the local PC.
N/A
Import Configure List
This function supports communication interfaces including RS232/RS485/MODBUS
TC/MC/SIEMEN TCP, which share a total of 600 mapping web addresses.
Notice:
Each communication interface can import up to 600 mapping addresses.
However, if RS232 has been mapped to 10 addresses and another 600
mapping addresses are imported, the 10 mapping address imported
previously will be covered.
If 10 addresses has been mapping to RS232, there would be only 590
addresses left for other communication interfaces to import. A warning
message will be displayed if exceeds the limit.
N/A
Read/Write
Set up the access permissions for the mapped register address;
Read-only:
The device regularly reads data from appointed registers in the
slave, but will not update the data to the slave
Write-only:
The device updates the data to the slave when the registers
values were changed, but will not read the data from the slave
Read/write:
The device regularly reads data from appointed registers in the
slave, will update the data to the slave when the registers values are
changed.
Read/Write
Slave ID
Set up the corresponding slave communication port. The value is between 1 and
247.
1
Controller
In master mode, device types options are:
Delta PLC:
Use this option for Delta DVP / AH / AS series PLCs
Other:
Use this option for non-Delta PLCs. HEX means hexadecimal
address; DEC means decimal address.
Delta DVP
PLC
Address Type
In master mode, the address type would changes with different options of controller
type.:
Delta PLC:
address types would be D/M/S/X/Y, which D is a word type and
M/S/X/Y are of bit type.
Other: Address type is
0x/1x/3x/4x/Swap
a)
0x: Coils(Modbus function code: 01/05), read-write.
b)
1x: Discrete Inputs(Modbus function code: 02), read only.
c)
3x: Input Registers (Modbus function code: 04) , read only.
d)
4x: Holding Registers (Modbus function code: 03/16), read-write.
e)
Swap: If using “double words” to read/write “holding registers”, before
reading or writing, the values in Hi Word and Low Word will be swapped
first.
D
Summary of Contents for DX-2100 Series
Page 3: ......
Page 7: ...4 6 2 4 Registers View 6 6 6 2 5 Alarm List 6 7 ...
Page 15: ...DX 2100 Series Industrial 3G Cloud Router 1 8 _1 Memo ...
Page 36: ...Chapter 2 Introduction to User Interface 2 21 2_ ...
Page 108: ...DX 2100 Series Industrial 3G Cloud Router 3 72 _3 MEMO ...
Page 146: ...DX 2100 Series Industrial 3G Cloud Router 5 24 _5 MEMO ...
Page 154: ...DX 2100 Series Industrial 3G Cloud Router 6 8 _6 MEMO ...