C h a p t e r 4 O p e r a t i o n s
4 - 7
4_
1.
Press ENTER on the parameter page and start setting after the number flashes.
2.
Press UP or DOWN to select the numeric.
3.
Press LEFT key move to next digit.
4.
Repeat step 2 to 3 until finishing 4-digits, press ENTER key to save and return to the next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.4.7 LCM Backlight (BLight)
LCM Backlight timer setting. The selectable range is 0 ~ 15 minutes, 0 means always light. The default value is 1.
Steps of setup are as follows:
1.
Press ENTER on the parameter page and start setting after the number flashes.
2.
Press UP or DOWN to select the numeric.
3.
Press LEFT key move to next digit.
4.
Repeat step 2 to 3 until finishing setting, press ENTER key to save and return to the next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.4.8 Default Display (Dsply)
The default page of the power meter can be selected by Voltage(V1)
、
Loop 1 current(I1)
、
Loop 2 current(I2)
、
Loop
3 current(I3)
、
Loop 4 current(I4)
、
Loop 5 current(I5)
、
Loop 1 power(P1)
、
Loop 2 power(P2)
、
Loop 3 power(P3)
、
Loop 4 power(P4)
、
Loop 5 power(P5)
、
Loop 1 positive energy(PE1)
、
Loop 2 positive energy(PE2)
、
Loop 3 positive
energy(PE3)
、
Loop 4 positive energy(PE4)
、
Loop 5 positive energy(PE5)
、
Loop 1 negative energy(NE1)
、
Loop 2
negative energy(NE2)
、
Loop 3 negative energy(NE3)
、
Loop 4 negative energy(NE4)
、
Loop 5 negative energy(NE5).
The default value is Voltage(V1).
Steps of setup are as follows:
1.
Press the ENTER key on the parameter page, the setting starts after the content flashes.
2.
Press UP or DOWN to select the parameter of default page.
3.
Press ENTER to save and return to next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.4.9 Number of Loops (Loop)